Project engineering
For project engineering a DP master engineering tool can be used like the
Siemens SIMATIC manager. Here you assign the according PROFIBUS
DP slave modules to the DP master.
A direct assignment takes place via the PROFIBUS address that you set at
the DP slave address selector.
By installing the corresponding GSD file the IM 353-1DP01 is listed at the
hardware catalog as "VIPA_353-1DP01 (DP-V0 or DP-V1)".
You'll find this at:
PROFIBUS DP
> Additional Field devices> I/O > VIPA_System_300V
The GSD files may be found at www.vipa.com at the "Service" part.
Depending on the installed GSD file the following modules are listed at the
hardware catalog:
Module
GSD file
VIPA 353-1DP01 (DP-V0)
VI0009AF.gsd
VIPA 353-1DP01 (DP-V1)
VI0109AF.gsd
Install the appropriate GSD file in your engineering tool. For more
information see manual of you engineering tool.
•
Mount your PROFIBUS system.
•
Start your project engineering tool with a new project.
•
Configure a master system and create a new PROFIBUS subnet.
•
For the project engineering of the IM 353-1DP01 take the "VIPA 353-
1DP01 (DPV0)" or "VIPA 353-1DP01 (DPV1)" for each functionality from
the hardware catalog and drag it to the DP master subnet.
•
Enter a PROFIBUS address between 1 and 99 into the properties of the
DP slave and set the same address at the address lever.
•
Parameterize the DP slave (see parameters).
•
Transfer your project to the PLC.
General
DP-V0/DP-V1
functionality by
GSD file
Project
engineering