background image

 

 

YASKAWA

YASKAWA

MANUAL NO.  TOE-C736-40.8

Upon receipt of the product and prior to initial operation, read these instructions 
thoroughly, and retain for future reference.

2C-RELAY OUTPUT CARD DO-02C

INSTRUCTIONS 

VARISPEED-616G5 OPTION CARD

Summary of Contents for VARISPEED-616G5

Page 1: ...MANUAL NO TOE C736 40 8 Upon receipt of the product and prior to initial operation read these instructions thoroughly and retain for future reference 2C RELAY OUTPUT CARD DO 02C INSTRUCTIONS VARISPEED 616G5 OPTION CARD ...

Page 2: ...ibed in CAUTION may result in a vital accident in some situations In either case follow these important items These are steps to be taken to insure proper operation and to avoid malfunctions etc CAUTION S The option card uses C MOS IC chips It may break if touched by bare fingers because of static electricity Be careful when handling S When removing the option card from the inverter for transporta...

Page 3: ...capability 250VAC 1A or lower 30VDC 1A or lower Terminal block TD Relay K1 for No 2 output Connector to inverter control board 3CN S p a c e r mounting hole Relay K2 for No 1 output Fig 1 2C relay output card DO 02C Before use 1 Before using DO 02C read this manual and the manual for the installation of the inverter 2 Before connecting DO 02C or external terminals turn OFF main power of the invert...

Page 4: ...y or damage Though the products have undergone rigorous inspection before shipping check the following for safety S Check the name written on the product to verify that ordered products have been delivered S Check for damage caused during transportation If there is anything uncertain on the structure contact your YASKAWA repre sentative ...

Page 5: ... Gently push DO 02C until the spacer engages the spacer hole of the option card on the control board Fix DO 02C tightly See part A of the side view 3 After installing DO 02C connect the inverter with peripheral devices and replace the cover of the inverter Spacer mounting hole Top Option A Option C Control board Option D 4CN Option A connector 2CN Option C connector 3CN Option D connector Connecto...

Page 6: ...lowing S If the card is to be used as a heavy current circuit for main circuit wiring or as any other type of circuit that emits much noise separate the cables from other signal cables S If the card is to be used as a signal circuit separate the cables from heavy current circuits main circuit wiring or any other power wiring The output relays of DO 02C are not for weak current signals If used for ...

Page 7: ...ng S Applicable wire sizes for terminal block TD are shown below Terminal MKDS1 series manufactured byPhoenix ContactGmbH Co mm2 AWG I A VAC V Thin twisted wire 1 16 16 250 Solid wire 1 5 14 16 250 UL 22 14 10 300 CSA 22 14 10 300 Terminal block TD side Connecting wire end 5 5 mm Notes on selecting cables Too thick a cable applies pressure to the option card and may lead to failure Too thin a cabl...

Page 8: ...ter Operation ready 26 07 During undervoltage UV detection 27 08 During baseblock NO contact output 28 09 Frequency reference mode 29 0A Run command mode 2A 0B Overtorque detection 1 NO contact output 2B 0C Loss of frequency reference 2C 0D Braking resistor fault 2D 0E Fault Faults other than CPF00 or CPF01 2E 0F 2F 10 Alarm 30 During torque limit 2 11 Fault reset command active 31 During speed li...

Page 9: ... Oper B1 04 Prohibition of reverse operation 0 1 0 0 Reverse enabled 1 Reverse disabled f f f f AI 14B AI 14 Input Set F2 01 Bi polar or uni polar inputselection 0 1 0 0 0 to 10V 1 10 to 10 V f f DI 08 DI 16H2 DI Input F3 01 Digital input option 0 to 8 1 0 BCD 1 1 BCD 0 1 2 BCD 0 01 3 BCD 1 Hz 4 BCD 0 1Hz 5 BCD 0 01Hz 6 BCD 5 digits input 7 Binary 100 255 4095 10000 f f AO Ch1 Select F4 01 Channel...