B.3 Parameter Table
518
YASKAWA ELECTRIC
SIEP C710636 02B YASKAWA U1000 Technical Manual
■
o2: Digital Operator Keypad Functions
■
o3: Copy Function
■
o4: Maintenance Monitor Settings
o1-10
(520H)
User-Set Display Units Maximum
Value
These settings define the display values when o1-03 is set to 3.
o1-10 sets the display value that is equal to the maximum output frequency.
o1-11 sets the position of the decimal position.
Min: 1
Max: 60000
o1-11
(521H)
User-Set Display Units Decimal
Display
Min: 0
Max: 3
<10> Default setting is determined by the control mode (A1-02).
<36> Default setting value is determined by the digital operator display selection (o1-03).
No. (Addr.)
Name
Description
Setting
Page
o2-01
(505H)
LO/RE (LOCAL/REMOTE) Key
Function Selection
0: Disabled
1: Enabled. LO/RE key switches between LOCAL and REMOTE operation.
Default: 1
Min: 0
Max: 1
o2-02
(506H)
STOP Key Function Selection
0: Disabled. STOP key is disabled in REMOTE operation.
1: Enabled. STOP key is always enabled.
Default: 1
Min: 0
Max: 1
o2-03
(507H)
User Parameter Default Value
0: No change.
1: Set defaults. Saves parameter settings as default values for a User Initialization.
2: Clear all. Clears the default settings that have been saved for a User Initialization.
Default: 0
Min: 0
Max: 2
o2-04
(508H)
Drive Model Selection
Enter the drive model. Setting required only if installing a new control board.
Default: Determined by
drive capacity
Min: –
Max: –
o2-05
(509H)
Frequency Reference Setting
Method Selection
0: ENTER key must be pressed to enter a frequency reference.
1: ENTER key is not required. The frequency reference can be adjusted using the up and down
arrow keys only.
Default: 0
Min: 0
Max: 1
o2-06
(50AH)
Operation Selection when Digital
Operator is Disconnected
0: The drive continues operating if the digital operator is disconnected.
1: A fault is triggered (oPr) and the motor coasts to stop.
Default: 0
Min: 0
Max: 1
o2-07
(527H)
Motor Direction at Power Up when
Using Operator
0: Forward
1: Reverse
This parameter requires that drive operation be assigned to the digital operator.
Default: 0
Min: 0
Max: 1
o2-09
(50DH)
Reserved
–
–
–
No. (Addr.)
Name
Description
Setting
Page
o3-01
(515H)
Copy Function Selection
0: Copy select
1: INV
→
OP READ (Read parameters from the drive, saving them onto the digital operator.)
2: OP
→
INV WRITE (Copy parameters from the digital operator, writing them to the drive.)
3: OP
→
INV VERIFY (Verify parameter settings on the drive to check if they match the data
saved on the operator.)
To read the drive’ parameter settings into the digital operator, set o3-02 to 1 (to allow reading).
Default: 0
Min: 0
Max: 3
o3-02
(516H)
Copy Allowed Selection
Selects whether the read operation (o3-01 = 1) is enabled or disabled.
0: Read operation prohibited
1: Read operation allowed
Default: 0
Min: 0
Max: 1
No. (Addr.)
Name
Description
Setting
Page
o4-01
(50BH)
Cumulative Operation Time
Setting
Sets the value for the cumulative operation time of the drive in units of 10 h.
Default: 0
Min: 0
Max: 9999
o4-02
(50CH)
Cumulative Operation Time
Selection
0: Logs power-on time
1: Logs operation time when the drive output is active (output operation time).
Default: 0
Min: 0
Max: 1
o4-03
(50EH)
Cooling Fan Operation Time
Setting
Sets the value of the fan operation time monitor U4-03 in units of 10 h.
Default: 0
Min: 0
Max: 9999
o4-05
(51DH)
Capacitor Maintenance Setting
Sets the value of the Maintenance Monitor for the capacitors. See U4-05 to check when the
capacitors may need to be replaced.
Default: 0%
Min: 0%
Max: 150%
No. (Addr.)
Name
Description
Setting
Page
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
SIEP_C710636_02B_1_0.book 518 ページ 2015年11月25日 水曜日 午後4時56分