No.
Parameter Name
Setting Range
Default
P1-06
Minimum Pump Speed
0.0 to E1-04
40.0 Hz
Note:
Unit range and resolution are determined by P1-07, Minimum Pump Speed Units. Setting P1-07 to 1 (RPM) will set a default value of 1800
RPM (VTC) and 2400 RPM (all others). Setting P1-07 to 0 Hz, (default) will set a default value of 40.0 Hz.
n
P1-07: Minimum Pump Speed Units
Sets the units for parameter P1–06. Changing P1-07 will reset P1-06 to the default value.
No.
Parameter Name
Setting Range
Default
P1-07
Minimum Pump Speed Units
0 to 1
0
n
P1-08: Low Feedback Level
Sets the level at which a Low Feedback alarm or fault will occur. When the PID feedback falls below the P1-08 setting for
the time set in P1-09, the drive will respond based on the setting in P1-10.
No.
Parameter Name
Setting Range
Default
P1-08
Low Feedback Level
0.0 PSI
<1> Range is 0.0 to 999.9 with sign-bit “-” indicating Delta to Setpoint.
Range is 0.0 to 6000.0 in drive software versions PRG: 8551 and earlier.
n
P1-09: Low Feedback Level Fault Delay Time
Sets the delay time after which a Low Feedback alarm or fault will occur. When the PID feedback falls below the P1-08 setting
for the time set in P1-09, the drive will respond based on the setting in P1-10.
No.
Parameter Name
Setting Range
Default
P1-09
Low Feedback Level Fault Delay Time
0 to 3600 s
10 s
n
P1-10: Low Feedback Selection
Selects the drive response to a Low Feedback condition. When the PID feedback falls below the P1-08 setting for the time set
in P1-09, the drive will respond based on the setting in P1-10.
No.
Parameter Name
Setting Range
Default
P1-10
Low Feedback Selection
0 to 2
0
Low feedback detection is enabled when:
• P1-08 > 0.0
• Drive is running in AUTO Mode, including sleep boost and feedback drop detection (standard PID, b5-09 = 0)
• Run Command is present (including sleep and timer operation) (inverse PID, b5-09 = 1)
Setting 0: Fault
When feedback drops below the P1-08 level for longer than the time set in P1-09, the drive will fault on the “LFB – Low
Feedback” fault and coast to a stop.
The digital output programmed to “Low Feedback” (H2-0
o
= 97) closes. The drive will also display the “Low Feedback –
Low FB Sensed” alarm. The digital output will remain closed until the fault is reset.
Setting 1: Alarm
When feedback drops below the P1-08 level for longer than the time set in P1-09, the digital output programmed to “Low
Feedback” (H2-0
o
= 97) closes and the drive displays the “Low Feedback – Low FB Sensed” alarm.
When feedback rises above the level determined by P1-08 and P1-14, or when one or more of the conditions that enable low
feedback detection are no longer true, the digital output will open and the alarm will clear.
Setting 2: Digital out only
When feedback drops below the P1-08 level for longer than the time set in P1-09, the digital output programmed to “Low
Feedback” (H2-0
o
= 97) closes.
When feedback rises above the level determined by P1-08 and P1-14, or when one or more of the conditions that enable low
feedback detection are no longer true, the digital output will open.