A1-08 = 3005
(A1-06 = 5)
General Ext HOA
A1-08 = 3006
(A1-06 = 6)
General HOA Keys
Parameter
Value
Parameter
Value
H3-06
1FH
H3-06
1FH
H3-10
0
H3-10
0
L5-04
180.0 s
L5-04
180.0 s
o1-06
0
o1-06
0
P1-05
0 s
P1-05
0 s
P1-06
0.0 Hz
P1-06
0.0 Hz
P4-12
0.0 Hz
P4-12
0.0 Hz
P4-17
0.0 min
P4-17
0.0 min
P5-01
0
P5-02
0.0 Hz
P5-03
1
P5-03
1
P5-04
0
-
-
Parameters Displayed Depending on A1-08 Setting
The following table shows which parameters are shown on the Pump Quick Setting menu depending on the A1-08 selection:
A1-08 = 3005
(A1-06 = 5)
General Ext HOA
A1-08 = 3006
(A1-06 = 6)
General HOA Keys
C1-01
C1-01
C1-02
C1-02
E2-01
E2-01
E2-04
E2-04
H1-02
H1-02
H1-03
H1-03
H1-05
H1-05
L5-01
L5-01
L5-04
L5-04
P1-06
P1-06
P5-05
P5-02
n
b1-01: Frequency Reference Selection 1
Selects the frequency reference source 1 for the REMOTE mode.
Note:
If a Run command is input to the drive but the frequency reference entered is 0 or below the minimum frequency, the RUN indicator LED
on the digital operator will light and the STOP indicator will flash.
No.
Parameter Name
Setting Range
Default
b1-01
Frequency Reference Selection 1
0 to 4
0
In order to run the drive and motor, the drive must receive a Run command and an Auto Setpoint command. Parameter b1-01
specifies the origin of the Auto setpoint when in AUTO Mode. Switch to AUTO mode by pressing the AUTO button on the
HOA keypad while the drive is stopped.
Note:
If a Run command is input to the drive without a corresponding Auto setpoint, the Run indicator on the HOA keypad will turn on and the
STOP indicator on the keypad will blink.
If the drive should follow the “HAND Reference” set by the HOA keypad, use HAND Mode by pressing the HAND key and
set P5-01 to “1: Hand Reference (P5-02).” The HAND reference can then be entered into the U1-01 monitor parameter in the
“-DRIVE- ” Menu.
The drive offers the ability to provide four types of “Auto Setpoint” reference sources. These Auto Setpoint reference sources
are determined by the setting of b1-01 and the drive set to AUTO Mode by pressing the AUTO key on the keypad.
Prior to programming, it is recommended to select the system units (P1-02) and the feedback device, Scaling (P1- 03) first.
P1-03 will automatically scale the drive setpoint.
Example: P1-02 = 1: PSI
P1-03 = 200, feedback range = 200 PSI.
4.7 Basic U1000 iQpump Setup and Application Preset Parameters
YASKAWA TOEPYAIUPW01A YASKAWA AC Drive - U1000 iQpump Matrix Drive User Manual
143
4
Start-Up Programming & Operation