
B.17 V/f Pattern Default Values
show the V/f pattern setting default values depending on the control mode and V/f pattern selection
(A1-02 and E1-03).
Table B.6 E1-03 V/f Pattern Settings for Drive Capacity: Models 4
o
0011 and 4
o
0014
No.
Unit
V/f Control
OLV
CLV
E1-03
-
0
1
2
3
4
5
6
7
8
9
A
B
C
D
E
F
E1-04
Hz
50.0
60.0
60.0
72.0
50.0
50.0
60.0
60.0
50.0
50.0
60.0
60.0
90.0
120.0
180.0
60.0
60.0
60.0
V
200.0
200.0
200.0
200.0
200.0
200.0
200.0
200.0
200.0
200.0
200.0
200.0
200.0
200.0
200.0
230.0
230.0
230.0
E1-06
Hz
50.0
60.0
50.0
60.0
50.0
50.0
60.0
60.0
50.0
50.0
60.0
60.0
60.0
60.0
60.0
60.0
60.0
–
E1-07
Hz
2.5
3.0
3.0
3.0
25.0
25.0
30.0
30.0
2.5
2.5
3.0
3.0
3.0
3.0
3.0
3.0
3.0
–
V
15.0
15.0
15.0
15.0
35.0
50.0
35.0
50.0
19.0
24.0
19.0
24.0
15.0
15.0
15.0
17.3
13.8
–
E1-09
Hz
1.3
1.5
1.5
1.5
1.3
1.3
1.5
1.5
1.3
1.3
1.5
1.5
1.5
1.5
1.5
1.5
0.5
–
V
9.0
9.0
9.0
9.0
8.0
9.0
8.0
9.0
11.0
13.0
11.0
15.0
9.0
9.0
9.0
10.2
2.9
–
<1> This value determines the default values for E1-04 through E1-10 (E3-04 through E3-10 for motor 2).
<2> Values shown here are specific to 200 V class drives. Double the value for 400 V class drives.
Table B.7 E1-03 V/f Pattern Settings for Drive Capacity: Models 2
o
0028 to 2
o
0192 and 4
o
0021 to 4
o
0124
No.
Unit
V/f Control
OLV
CLV
E1-03
-
0
1
2
3
4
5
6
7
8
9
A
B
C
D
E
F
E1-04
Hz
50.0
60.0
60.0
72.0
50.0
50.0
60.0
60.0
50.0
50.0
60.0
60.0
90.0
120.0
180.0
60.0
60.0
60.0
V
200.0
200.0
200.0
200.0
200.0
200.0
200.0
200.0
200.0
200.0
200.0
200.0
200.0
200.0
200.0
230.0
230.0
230.0
E1-06
Hz
50.0
60.0
50.0
60.0
50.0
50.0
60.0
60.0
50.0
50.0
60.0
60.0
60.0
60.0
60.0
60.0
60.0
–
E1-07
Hz
2.5
3.0
3.0
3.0
25.0
25.0
30.0
30.0
2.5
2.5
3.0
3.0
3.0
3.0
3.0
3.0
3.0
–
V
14.0
14.0
14.0
14.0
35.0
50.0
35.0
50.0
18.0
23.0
18.0
23.0
14.0
14.0
14.0
16.1
12.7
–
E1-09
Hz
1.3
1.5
1.5
1.5
1.3
1.3
1.5
1.5
1.3
1.3
1.5
1.5
1.5
1.5
1.5
1.5
0.5
–
V
7.0
7.0
7.0
7.0
6.0
7.0
6.0
7.0
9.0
11.0
9.0
13.0
7.0
7.0
7.0
8.1
2.3
–
<1> This value determines the default values for E1-04 through E1-10 (E3-04 through E3-10 for motor 2).
<2> Values shown here are specific to 200 V class drives. Double the value for 400 V class drives.
Table B.8 E1-03 V/f Pattern Settings for Drive Capacity: Models 2
o
0248 and 4
o
0156 to 4
o
0930
No.
Unit
V/f Control
OLV
CLV
E1-03
-
0
1
2
3
4
5
6
7
8
9
A
B
C
D
E
F
E1-04
Hz
50.0
60.0
60.0
72.0
50.0
50.0
60.0
60.0
50.0
50.0
60.0
60.0
90.0
120.0
180.0
60.0
60.0
60.0
E1-05
V
200.0
200.0
200.0
200.0
200.0
200.0
200.0
200.0
200.0
200.0
200.0
200.0
200.0
200.0
200.0
230.0
230.0
230.0
E1-06
Hz
50.0
60.0
50.0
60.0
50.0
50.0
60.0
60.0
50.0
50.0
60.0
60.0
60.0
60.0
60.0
60.0
60.0
–
E1-07
Hz
2.5
3.0
3.0
3.0
25.0
25.0
30.0
30.0
2.5
2.5
3.0
3.0
3.0
3.0
3.0
3.0
3.0
–
E1-08
V
12.0
12.0
12.0
12.0
35.0
50.0
35.0
50.0
15.0
20.0
15.0
20.0
12.0
12.0
12.0
13.8
12.7
–
E1-09
Hz
1.3
1.5
1.5
1.5
1.3
1.3
1.5
1.5
1.3
1.3
1.5
1.5
1.5
1.5
1.5
1.5
0.5
–
E1-10
V
6.0
6.0
6.0
6.0
5.0
6.0
5.0
6.0
7.0
9.0
7.0
11.0
6.0
6.0
6.0
6.9
2.3
–
<1> This value determines the default values for E1-04 through E1-10 (E3-04 through E3-10 for motor 2).
<2> Values shown here are specific to 200 V class drives. Double the value for 400 V class drives.
B.17 V/f Pattern Default Values
YASKAWA ELECTRIC SIEP C710636 04D U1000 Industrial MATRIX Drive Technical Manual
587
B
Parameter List
Summary of Contents for U1000 iQpump Drive
Page 705: ......