L2: Momentary Power Loss Ride-Thru
No.
(Addr.
Hex)
Name
LCD Display
Description
Values
Page
L2-01
(0485)
Momentary Power Loss
Operation Selection
PwrL Selection
0: Disabled
1: Enbl with Timer
2: Enbl whl CPU act
All Modes
0: Disabled. Drive trips on Uv1 fault when power is lost.
1: Recover within the time set in L2-02. Uv1 will be detected if
power loss is longer than L2-02.
2: Recover as long as CPU has power. Uv1 is not detected.
Default: 0
Range: 0 to 2
L2-02
(0486)
Momentary Power Loss
Ride-Thru Time
PwrL Ridethru t
All Modes
Sets the Power Loss Ride-Thru time. Enabled only when L2-01
= 1 or 3.
Default: 0.5 s
Min.: 0.0
Max.: 2.5
L2-03
(0487)
Momentary Power Loss
Minimum Baseblock
Time
PwrL Baseblock t
All Modes
Sets the minimum wait time for residual motor voltage decay
before the drive output reenergizes after performing Power Loss
Ride-Thru.
Increasing the time set to L2-03 may help if overcurrent or
overvoltage occur during Speed Search or during DC Injection
Braking.
Min.: 0.1 s
Max.: 5.0 s
L2-04
(0488)
Momentary Power Loss
Voltage Recovery Ramp
Time
PwrL V/F Ramp t
V/f
OLV/PM
V/f w PG
AOLV/PM
OLV
CLV/PM
CLV
V/f
V/f w PG
OLV
CLV
V/f
OLV/PM
V/f w PG
AOLV/PM
OLV
CLV/PM
CLV
V/f
V/f w PG
OLV
CLV
Sets the time for the output voltage to return to the preset V/f
pattern during Speed Search.
Min.: 0.0 s
Max.: 5.0 s
L2-07
(048B)
Momentary Power Loss
Voltage Recovery
Acceleration Time
KEB Accel Time
All Modes
Sets the time to accelerate to the frequency reference when
momentary power loss is over. If set to 0.0, the active acceleration
time (C1-01, C1-03, C1-05, or C1-07) is used.
Default: 0.00 s
Min.: 0.00
Max.: 6000.0
L2-13
(04CD)
Input Power Frequency
Fault Detection Gain
FDV Detect Gain
All Modes
Set the gain to use to detect power supply frequency fault (Fdv).
Default: 1.0
Min.: 0.1
Max.: 2.0
L2-21
(04D5)
Low Input Voltage
Detection Level
AVV Detect evel
All Modes
Set the level at which to detect a low input voltage.
Default: 150 V
Min.: 100 V
L2-27
(04F7)
Power Supply
Frequency Fault
Detection Width
FDV Detect Width
All Modes
Sets the frequency width to use to detect power supply frequency
fault (Fdv).
Default: 6.0 Hz
Min.: 3.0 Hz
Max.: 20.0 Hz
<1> Default setting is determined by parameters C6-01, Drive Duty Selection, and o2-04, Drive Model Selection.
<2> Setting range value is dependent on parameter C1-10, Accel/Decel Time Setting Units. When C1-10 = 0 (units of 0.01 seconds), the setting range
becomes 0.00 to 600.00 seconds.
<3> Values shown are specific to 200 V class drives. Double the value for 400 V class drives.
u
L3: Stall Prevention
No.
(Addr.
Hex)
Name
LCD Display
Description
Values
Page
L3-01
(048F)
Stall Prevention
Selection during
Acceleration
StallP Accel Sel
0: Disabled
1: General Purpose
3: iLim Mode
V/f
OLV/PM
V/f w PG
AOLV/PM
OLV
CLV/PM
CLV
V/f
OLV/PM
V/f w PG
OLV
0: Disabled.
1: Enabled. General purpose. Acceleration is paused as long as
the current is above the L3-02 setting.
3: Enabled (Current Limit). The acceleration rate is automatically
adjusted while limiting the output current at the setting value of
the stall prevention level (L3-02).
Note:
Setting 3 is not available when using OLV/PM.
Default: 1
Range: 0, 1, 3
L3-02
(0490)
Stall Prevention Level
during Acceleration
StallP Accel Lvl
V/f
OLV/PM
V/f w PG
AOLV/PM
OLV
CLV/PM
CLV
V/f
OLV/PM
V/f w PG
OLV
Used when L3-01 = 1 or 3. 100% is equal to the drive rated
current.
Min.: 0%
Max.: 150%
B.10 L: Protection Function
550
YASKAWA ELECTRIC SIEP C710636 04D U1000 Industrial MATRIX Drive Technical Manual