No.
Name
Setting Range
Default
o4-05
Capacitor Maintenance Setting
0 to 150%
0%
n
o4-07: DC Bus Pre-Charge Relay Maintenance Setting
Sets the value of the softcharge bypass relay maintenance time displayed in U4-06 as a percentage of the total expected
performance life. Reset this value to 0 after replacing the bypass relay.
Note:
The actual maintenance time will depend on the environment where the drive is used.
No.
Name
Setting Range
Default
o4-07
DC Bus Pre-charge Relay Maintenance Setting
0 to 150%
0%
n
o4-11: U2, U3 Initialization
Resets the fault trace and fault history monitors (U2-
oo
and U3-
oo
).
Note:
Initializing the drive using A1-03 does not reset these monitors.
No.
Name
Setting Range
Default
o4-11
U2, U3 Initialization
0, 1
0
Setting 0: No Action
The drive keeps the previously saved record concerning fault trace and fault history.
Setting 1: Reset Fault Data
Resets the data for the U2-
oo
and U3-
oo
monitors. Setting o4-11 to 1 and pressing the ENTER key erases fault data and
returns the display to 0.
n
o4-12: kWh Monitor Initialization
Resets the electric power (U9-01 to U9-03) and regenerative power (U9-04 to U9-06). Resets electric power rate (U9-07 to
U9-10) and regenerative power rate (U9-11 to U9-14).
No.
Name
Setting Range
Default
o4-12
kWh Monitor Initialization
0, 1
0
Setting 0: No Action
Setting 1: Reset kWh Data
n
o4-13: Number of Run Commands Counter Initialization
Resets the Run command counter displayed in U4-02. Initializing the drive or cycling the power does not reset this monitor.
No.
Name
Setting Range
Default
o4-13
Number of Run Commands Counter Initialization
0, 1
0
Setting 0: No Action
The Run command data are kept.
Setting 1: Number of Run Commands Counter
Resets the Run command counter. The monitor U4-02 will show 0. Setting o4-13 to 1 and pressing the ENTER key erases the
counter value and returns the display to 0.
n
o4-19: Power Unit Price
Sets the price per 1 kWh to calculate the power rate displayed for total consumed power (U9-07 to U9-10) and total regenerated
power (U9-11 to U9-14).
No.
Name
Setting Range
Default
o4-19
Power Unit Price
0.00 to 650.00
000.00
u
q: DriveWorksEZ Parameters
These parameters are reserved for use with DriveWorksEZ. Refer to the DriveWorksEZ manual for more information.
5.10 o: Operator Related Settings
YASKAWA ELECTRIC SIEP C710636 04D U1000 Industrial MATRIX Drive Technical Manual
349
5
Parameter Details