Frequency reference
Frequency reference
+
L4-02
Frequency reference
– L4-02
L4-01
L4-01
+
L4-02
L4-01
– L4-02
Frequency reference
Frequency reference
+
L4-02
Frequency reference
– L4-02
–L4-01
–L4-01
+
L4-02
–L4-01
– L4-02
During
Forward
During Reverse
Output frequency
0 Hz
OFF
OFF
OFF
ON
ON
ON
ON
Output frequency
User Set
Speed Agree 1
Figure 5.69 User Set Speed Agree 1 Time Chart
Refer to L4-01, L4-02: Speed Agree Detection Level and Detection Width on page 320
for more instructions.
Setting 4: Frequency Detection 1
The output opens when the output frequency or motor speed (CLV, CLV/PM) rises above the detection level set in L4-01 plus
the detection width set in L4-02. The terminal remains open until the output frequency or motor speed fall below the level set
in L4-01.
Status
Description
Open
Output frequency or motor speed exceeded L4-01 + L4-02.
Closed
Output frequency or motor speed is below L4-01 or has not exceeded L4-01 + L4-02.
Note:
Frequency detection works in forward and reverse. The value of L4-01 is used as the detection level for both directions.
L4-02
Frequency
detection 1 <1>
ON
OFF
L4-02
L4-01
L4-01
Output Frequency
or Motor Speed
Figure 5.70 Frequency Detection 1 Time Chart
<1> This is the time chart when L4-07 (Speed Agree Detection Selection) is set to 1 (detection always enabled). The default
setting for L4-07 is 0 (no detection during baseblock). When L4-07 is set to 0, the terminal opens during baseblock.
Refer to L4-01, L4-02: Speed Agree Detection Level and Detection Width on page 320
for more details.
Setting 5: Frequency Detection 2
The output closes when the output frequency or motor speed (CLV, CLV/PM) is above the detection level set in L4-01. The
terminal remains closed until the output frequency or motor speed fall below L4-01 minus the setting of L4-02.
Status
Description
Open
Output frequency or motor speed is below L4-01 minus L4-02 or has not exceeded L4-01.
Closed
Output frequency or motor speed exceeded L4-01.
Note:
Frequency detection works in forward and reverse. The value of L4-01 is used as the detection level for both directions.
5.7 H: Terminal Functions
290
YASKAWA ELECTRIC SIEP C710636 04D U1000 Industrial MATRIX Drive Technical Manual