11 Drive Control, Duty Modes, and Programming
54
YASKAWA
TOEPC71061782C GA800 Drive Installation & Primary Operation
Table 11.3 EZ Tuning Mode Selection
Type
T4-01
Application Conditions and Benefits
A1-02 = 8
[EZOLV]
Motor Parameter Setting
0
Set the motor parameters.
Yes
Line-to-Line Resistance
1
Select this tuning mode after you replace the drive, motor, and motor cables.
Yes
◆
Drive Parameters
Icon
Description
The parameter is available when operating the drive with V/f Control.
The parameter is available when operating the drive with Closed Loop V/f Control.
The parameter is available when operating the drive with Open Loop Vector Control.
The parameter is available when operating the drive with Closed Loop Vector Control.
The parameter is available when operating the drive with Advanced Open Loop Vector Control.
The parameter is available when operating the drive with Open Loop Vector Control for PM.
The parameter is available when operating the drive with Advanced Open Loop Vector Control for PM.
The parameter is available when operating the drive with Closed Loop Vector Control for PM.
The parameter is available when operating the drive with EZ Open Loop Vector Control.
RUN
You can change the parameter setting during drive operation.
Note:
Gray icons identify parameters that are not available in the specified control method.
This section shows the most common parameters for applications. Refer to this table when you set parameters.
No.
(Hex.)
Name
Description
A1-00
(0100)
RUN
Language Selection
Sets the language for the LCD keypad.
0 : English
1 : Japanese
2 : German
3 : French
4 : Italian
5 : Spanish
6 : Portuguese
7 : Chinese
8 : Czech
9 : Russian
10 : Turkish
11 : Polish
12 : Greek
A1-02
(0102)
Control Method Selection
Sets the control method for the drive application and the motor.
0 : V/f Control
1 : V/f Control with Encoder
2 : Open Loop Vector
3 : Closed Loop Vector
4 : Advanced Open Loop Vector
5 : PM Open Loop Vector
6 : PM Advanced Open Loop Vector
7 : PM Closed Loop Vector
8 : EZ Vector Control
A1-03
(0103)
Initialize Parameters
Sets parameters to default values.
0 : No Initialization
1110 : User Initialization
2220 : 2-Wire Initialization
3330 : 3-Wire Initialization
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV