TOEPC71061782C GA800 Drive Installation & Primary Operation
51
Note:
•
Set
H3-02, H3-10 = 0 [Terminal A1 Function Selection, Terminal A2 Function Selection = Frequency Reference]
to set A1 and A2 to
frequency reference. The drive will add the analog input values together to make the frequency reference.
•
Use tweezers or a jig with a tip width of approximately 0.8 mm (0.03 in) to set DIP switches.
•
Set DIP switch S4 to
“
AI
”
to use terminal A3 as an analog input (voltage/current) terminal. The default setting for DIP switch S4 is
“
AI
”
.
■
Set MFAI Terminal A3 to PTC Input
Set terminal A3 as an MFAI or as the PTC input for motor overload protection.
Use DIP switch S4 to set the input function.
Figure 10.15 Location of DIP Switch S4
Terminal
DIP switch S4
Description
A3
AI
(Default)
Functions as an MFAI terminal.
Set
H3-06 [Terminal A3 Function Selection]
to set the input function.
PTC
Functions as the PTC input terminal.
Set
H3-06 = E [Motor Temperature (PTC Input)]
.
Set S1-3 to
“
V
”
for voltage input.
■
Set Output Signals for MFAO Terminals FM, AM
Set the signal type for terminals AM and FM to voltage or current output. Use jumper switch S5 and
H4-07, H4-08
[Terminal FM Signal Level Select, Terminal AM Signal Level Select]
to set the signal type.
Figure 10.16 Location of Jumper Switch S5