B.3 Parameter Table
YASKAWA ELECTRIC
SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual
361
Pa
ra
met
er
Li
st
B
U3-15
Cumulative Operation Time
at 5th Most Recent Fault
Displays the cumulative operation time at the fifth most
recent fault.
No signal output
avail.
1 h
A A A
80E
U3-16
Cumulative Operation Time
at 6th Most Recent Fault
Displays the cumulative operation time at the sixth most
recent fault.
No signal output
avail.
1 h
A A A
80F
U3-17
Cumulative Operation Time
at 7th Most Recent Fault
Displays the cumulative operation time at the seventh
most recent fault.
No signal output
avail.
1 h
A A A
810
U3-18
Cumulative Operation Time
at 8th Most Recent Fault
Displays the cumulative operation time at the eighth most
recent fault.
No signal output
avail.
1 h
A A A
811
U3-19
Cumulative Operation Time
at 9th Most Recent Fault
Displays the cumulative operation time at the ninth most
recent fault.
No signal output
avail.
1 h
A A A
812
U3-20
Cumulative Operation Time
at 10th Most Recent Fault
Displays the cumulative operation time at the tenth most
recent fault.
No signal output
avail.
1 h
A A A
813
U4: Maintenance Monitors
Use U4 parameters to display drive maintenance information.
U4-01
Cumulative Operation Time
Displays the cumulative operation time of the drive. The
value for the cumulative operation time counter can be
reset in parameter o4-01. Use parameter o4-02 to
determine if the operation time should start as soon as the
power is switched on or only while the run command is
present. The maximum number displayed is 99999, after
which the value is reset to 0.
No signal output
avail.
1 h
A A A
4C
U4-02
Number of Run Commands
Displays the number of times the run command is
entered. Reset the number of run commands using
parameter o4-13. This value will reset to 0 and start
counting again after reaching 65535.
No signal output
avail.
–
A A A
75
U4-03
Cooling Fan Operation
Time
Displays the cumulative operation time of the cooling
fan. The default value for the fan operation time is reset in
parameter o4-03. This value will reset to 0 and start
counting again after reaching 99999.
No signal output
avail.
1 h
A A A
67
U4-04
Cooling Fan Maintenance
Displays main cooling fan usage time in as a percentage
of their expected performance life. Parameter o4-03 can
be used to reset this monitor.
No signal output
avail.
1%
A A A
7E
U4-05
Capacitor Maintenance
Displays main circuit and control capacitor usage time in
as a percentage of their expected performance life. As the
ambient temperature affects the lifespan of these
capacitors, the temperature must be set to parameter L8-
12. The maintenance of the capacitors is needed when
U4-05 = 100%. Reset U4-05 using parameter o4-05.
No signal output
avail.
1%
A A A
7C
U4-06
Soft Charge Bypass Relay
Maintenance
Displays the soft charge bypass relay maintenance time as
a percentage of the estimated product life. Parameter o4-
07 can be used to reset this monitor.
No signal output
avail.
1%
A A A
7D6
U4-07
IGBT Maintenance
Displays IGBT usage time as a percent of expected
performance life. Parameter o4-09 can be used to reset
this monitor.
No signal output
avail.
1%
A A A
7D7
U4-08
Heatsink Temperature
Displays the heatsink temperature.
No signal output
avail.
1 °C A A A
68
U4-09
LED Check
Lights all segments of the LED to verify that the display
is working properly.
No signal output
avail.
–
A A A
3C
U4-10
kWh, Lower 4 Digits
Monitors the drive output power. The value is shown as a
9 digit number displayed across two monitor parameters,
U4-10 and U4-11.
Example:
12345678.9 kWh is displayed as:
U4-10: 678.9 kWh
U4-11: 12345 MWh
No signal output
avail.
kWh A A A
5C
U4-11
kWh, Upper 5 Digits
MWh A A A
5D
U4-13
Peak Hold Current
Displays the peak hold current during run.
10 V: Motor rated
current
0.01A
A A A
7CF
U4-14
Peak Hold Output
Frequency
Displays the output frequency when operating at the peak
hold current.
10 V: Max
frequency
0.01H
z
A A A
7D0
No.
Name
Description
Analog Output
Level
Unit
Control
Mode
Addr.
Hex
V/f OL
V
P
M