5.7 H: Terminal Functions
YASKAWA ELECTRIC
SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual
193
P
a
ra
me
te
r D
e
ta
ils
5
Figure 5.58
Figure 5.58 Frequency Detection 1 Time Chart
Refer to L4-01, L4-02: Speed Agreement Detection Level and Detection Width on page 223
Setting 5: Frequency Detection 2
Output closes whenever the output frequency or motor speed (CLV, CLV/PM) is above the detection level set in L4-01.
The terminal remains closed until the output frequency or motor speed falls below L4-01 minus the setting of L4-02.
Note:
Frequency detection works in both forward and reverse. The value of L4-01 is used as the detection level for both directions.
Figure 5.59
Figure 5.59 Frequency Detection 2 Time Chart
Refer to L4-01, L4-02: Speed Agreement Detection Level and Detection Width on page 223
Setting 6: Drive ready
Output closes whenever the drive is ready to operate the motor. The terminal will not close under the conditions listed
below, and any Run commands will be disregarded.
• When the power is shut off
• During a fault
• When the drive’s internal power supply has malfunctioned
• When a parameter setting error makes it impossible to run
• Although stopped, an overvoltage or undervoltage situation occurs
• While editing a parameter in the Programming Mode (when b1-08 = 0)
Setting 7: DC bus undervoltage
Output closes whenever the DC bus voltage or control circuit power supply drops below the trip level set in L2-05. A
fault in the DC bus circuit will also cause the terminal to set for “DC bus undervoltage” to close.
Setting 8: During baseblock (N.O.)
Output closes to indicate that the drive is in a baseblock state. While in baseblock, output transistors do not switch and no
main circuit voltage is output.
Status
Description
Open
Output frequency or motor speed is below L4-01 minus L4-02 or has not exceeded L4-01.
Closed
Output frequency or motor speed exceeded L4-01.
Status
Description
Open
DC bus voltage is above the level set to L2-05
Closed
DC bus voltage has fallen below the trip level set to L2-05.
L4-02
Frequency
detection 1
ON
OFF
L4-02
L4-01
L4-01
Output Frequency
or Motor Speed
L4-02
Frequency
Detection 2
ON
OFF
L4-02
L4-01
L4-01
Output Frequency
or Motor Speed