3 Electrical Installation
YASKAWA Europe
TOEP C710606 101A - V1000 MMD IP65 Motor Mounted Drive - Quick Start Guide
EN 25
ENGLISH
Wiring Specification
Main Circuit
Use the wire gauges listed up in the table below when wiring the main circuit. Make sure not
to exceed the given tightening torque values.
Input Fuse Selection
Branch circuit protection shall be provided by any of the following:
• Non-time delay Class J, T, or CC fuses sized at 300% of the drive input rating
Note:
Exceptional models are A6T20 with 4A0005, and A6T25 with 4A0007.
• Time delay Class J, T, or CC fuses sized at 175% of the drive input rating
• Time-delay Class RK5 fuses sized at 225% of the drive input rating
Model
V1MC-A
Filter Terminal Sizes L1, L2, L3
Recom. Motor cable
(mm²)
Applicable Gauge
(mm²)
Screw Size
Tightening Torque
(N×m (lb.in.))
40004
2.5
2.5 to 6
M5
2.0 to 2.5 (17.7 to 22.1)
40005
40007
40009
40011
Model
V1MC-A
Non-Time Delay
Class-T Fuse Type
(Manufacturer: Ferraz)
600 Vac, 200 kAIR
Fuse Ampere
Rating (A)
Fuse Type
(Manufacturer:
Bussmann)
500 Vac, 200 kAIR
Fuse Ampere
Rating (A)
40004
A6T15
15
FWH-50B
50
40005
A6T20
20
FWH-70B
70
40007
A6T25
25
FWH-70B
70
40009
A6T25
25
FWH-90B
90
40011
A6T30
30
FWH-90B
90