10 Troubleshooting
YASKAWA ELECTRIC
SIEP C730600 89C YASKAWA AC Drive Option SI-EP3 Technical Manual
53
Option Fault Monitors U6-98 and U6-99
The option can declare error/warning conditions via drive monitor parameters on the drive keypad as shown in
.
Table 31 Option Fault Monitor Descriptions
Two drive monitor parameters, U6-98 and U6-99 assist in network troubleshooting:
• U6-98 displays the first declared fault since the last power cycle. U6-98 is only cleared upon drive power-up.
• U6-99 displays the present option SI-EP3 status. U6-99 is cleared upon a network-issued fault reset and upon
power-up.
If another fault occurs while the original fault is still active, parameter U6-98 retains the original fault value and U6-99
stores the new fault status value.
Option Compatibility
Users may connect up to 3 options simultaneously depending on the type of option.
Refer to
for details.
Table 32 Option Compatibility
Fault Condition
Fault Declared
Status Value
(U6-98/U6-99)
Description
No Fault
N/A
0
No faults.
Force Fault
EF0
3
Network sent a message to force this node to the fault state.
Network Link Down
bUS
1300
No network link to option board.
Network Failure
bUS
1301
Connection with PLC Timeout.
Default MAC Address
None
1303
Factory default MAC Address programmed into the option. Return for
reprogramming.
No IP Address
None
1304
No IP Address has been programmed into the option.
No Station Name
None
1305
No Station Name has been programmed into the option.
Bad Station Name
Programmed
None
1306
Station Name Programmed is invalid and must be reprogrammed.
Init. Failure
None
1307
Initialize error on power-up.
Permanent
Communication Loss
bUS
1308
Fatal error in MAC/PHY hardware, requires power cycle to recover.
Bad IP Configuration
None
1309
Invalid IP/subnet/gateway address programmed into F7-01 to F7-12.
Option Card
<1> When connecting two PG option cards, use both CN5-B and CN5-C. When connecting only one PG option card, use the CN5-C connector.
<2> Not available for the application with Motor 2 Selection.
<3> Not available with 1000-Series drive models with a capacities between 450 and 630 kW.
<4> When you use the input status of AI-A3 and DI-A3 as a monitor, you can connect AI-A3 and DI-A3 to CN5-A, CN5-B, or CN5-C.
Connector
Number of Cards Possible
PG-B3, PG-X3
CN5-B, C
PG-RT3
CN5-C
1
DO-A3, AO-A3
CN5-A, B, C
1
SI-C3, SI-N3, SI-P3, SI-S3, SI-T3, SI-ET3,
SI-ES3, SI-B3, SI-M3, SI-W3
,
, SI-EP3, AI-A3
,
SI-EN3D, SI-EM3D
CN5-A
1