![YASKAWA SI-EP3/V Installation Manual Download Page 33](http://html2.mh-extra.com/html/yaskawa/si-ep3-v/si-ep3-v_installation-manual_3235232033.webp)
YASKAWA
TOEP YEACOM 06A V1000 Option PROFINET SI-EP3/V Installation Manual
33
7 Procedure B
7
Procedure B
Use
Procedure B
steps to install the option on drives with a NEMA Type 4X/IP66
enclosures or with the enclosure type digit G within the model number.
◆
Procedure B Steps
DANGER!
Electrical Shock Hazard. Do not connect or disconnect wiring while the power is on. Failure to
comply will result in death or serious injury. Before installing the option, disconnect all power to the drive.
The internal capacitor remains charged even after the power supply is turned off. The charge indicator LED
will extinguish when the DC bus voltage is below 50 Vdc. To prevent electric shock, wait at least five minutes
after all indicators are off and measure the DC bus voltage level to confirm safe level.
NOTICE:
Damage to Equipment. Observe proper electrostatic discharge procedures (ESD) when handling
the option, drive, and circuit boards. Failure to comply may result in ESD damage to circuitry.
1.
Shut off power to the drive, wait at least five minutes after confirming the DC bus
voltage is safe, then loosen the bolts that fasten the front cover in place and remove
the front cover.
2.
Press firmly on the connector release tab holding the LED operator cable (CN1) in
place and disconnect the cable.
Figure 26
Figure 26 Remove the Drive Front Cover
Remove LED operator cable
Connector release tab
Front cover
Front cover bolt
Drive
CN1 port