53
Note:
Set bits that you do not use to 0. Do not write to reserved registers.
Table 7.2 Command Register Data
Register Number
(Hex.)
Description
0000
Reserved
0001
Operation Commands and Multi-function Inputs
bit0
H5-12 = 0 [Run Command Method Selection = FWD/
Stop, REV/Stop]
: FWD/Stop
1: Forward operation in progress
0: Stop
H5-12 = 1 [Run Command Method Selection = Run/
Stop, FWD/REV]
: Run/Stop
1: Run
0: Stop
bit1
H5-12 = 0 [Run Command Method Selection = FWD/
Stop, REV/Stop]
: REV/Stop
1: Reverse Operation
0: Stop
H5-12 = 1 [Run Command Method Selection = Run/
Stop, FWD/REV]
: FWD/REV
1: Reverse run
0: Forward run
bit2
External Fault (EF0 [Option Card External Fault])
bit3
Fault Reset
bit4
Multi-Function Input 1
bit5
Multi-Function Input 2
bit6
Multi-Function Input 3
bit7
Multi-Function Input 4
bit8
Multi-Function Input 5
bit9
Multi-Function Input 6
bit A
Multi-Function Input 7
bit B
Multi-Function Input 8
bit C - F
Reserved