Sigma II User’s Manual
Chapter 7: Using the Digital Operator
7 - 33
7.2.5
Clearing Alarm Traceback Data
This procedure clears the alarm history, which stores the alarms generated in the
servo amplifier. After clearing, each alarm in the alarm history is set to A.- -, which
is not an alarm code. Refer to
7.2.1 Operation in Alarm Traceback Mode
for details.
Follow the procedure below to clear the alarm traceback data.
Using the Hand-held Digital Operator
1.
Press the
DSPL/SET
key to select the auxiliary function mode.
2.
Select the parameter Fn006.
Press the
Left Arrow
or
Right Arrow
key to select the digit.
Press the
Up Arrow
or
Down Arrow
key to change the value.
3.
Press the
DATA/ENTER
key, and the display will be as shown below.
4.
Press the
MODE/SET
key to clear the alarm traceback data. The following
display will flash for one second, and, after the alarm traceback data is cleared,
the display will return to the one in the above step 3.
5.
Press the
DATA/ENTER
key to return to the parameter code display.
This completes the alarm traceback data clearing procedure.
Flashing for
one second
Summary of Contents for SGMAH
Page 1: ...Sigma II Series Servo System User s Manual...
Page 2: ......
Page 4: ...ii This page intentionally left blank...
Page 6: ...iv This page intentionally left blank...
Page 10: ...Sigma II User s Manual Table of Contents Preface viii Notes...
Page 17: ...Sigma II User s Manual Table of Contents Preface xv C 6 Torque Control Mode C 9...
Page 18: ...Sigma II User s Manual Table of Contents Preface xvi...
Page 38: ...Sigma II User s Manual Chapter 2 Installation 2 10 NOTES...
Page 472: ...Sigma II User s Manual Appendix C Examples of Standard Connections C 10 Notes...
Page 487: ......