Sigma II User’s Manual
Chapter 5: Parameter Settings and Functions
5-111
MCCB or Fuse According to Power Capacity
The following table shows the MCCB or fuse capacity for each power supply
capacity.
*1
This is the net value at the rated load. When actually selecting fuses, determine the capacity with enough
margin for peak power operation.
*2
Operating characteristics (at 25°C): 2 seconds or more for 200%, 0.01 second or more for 700%
Notes: 1.
A fast-operating fuse cannot be used because the servo amplifier power supply is a capacitor
input type. A fast-operating fuse may blow when the power is turned ON.
2.
SGDH servo amplifiers do not have built-in ground protection circuits. To configure a safer
system, install a ground fault interrupter with or without a circuit breaker for protection against
overload and short circuit conditions.
Main Circuit
Power
Supply
Servo Amplifier
Model
Applicable Motor
Power Capacity per
Servo Amplifier
(kVA)
*1
Current Capacity per
MCCB or Fuse
(A
rms
)
*1, *2
Capacity
(kW)
SGDH-
Single-phase,
100V
0.03
A3BE
SGMAH-A3B
0.15
4
0.05
A5BE
SGMAH-A5B
0.25
0.10
01BE
SGMAH-01B
0.40
SGMPH-01B
0.20
02BE
SGMAH-02B
0.60
6
SGMPH-02B
Single-phase,
200V
0.03
A3AE
SGMAH-A3A
0.20
4
0.05
A5AE
SGMAH-A5A
0.25
0.10
01AE
SGMAH-01A
0.40
SGMPH-01A
0.20
02AE
SGMAH-02A
0.75
SGMPH-02A
0.40
04AE
SGMAH-04A
1.2
8
SGMPH-04A
0.75
08AE-S
SGMAH-08A
2.1
11
SGMPH-08A
1.50
15AE-S
SGMPH-15A
4.0
19
Summary of Contents for SGMAH
Page 1: ...Sigma II Series Servo System User s Manual...
Page 2: ......
Page 4: ...ii This page intentionally left blank...
Page 6: ...iv This page intentionally left blank...
Page 10: ...Sigma II User s Manual Table of Contents Preface viii Notes...
Page 17: ...Sigma II User s Manual Table of Contents Preface xv C 6 Torque Control Mode C 9...
Page 18: ...Sigma II User s Manual Table of Contents Preface xvi...
Page 38: ...Sigma II User s Manual Chapter 2 Installation 2 10 NOTES...
Page 472: ...Sigma II User s Manual Appendix C Examples of Standard Connections C 10 Notes...
Page 487: ......