an R, S, or T
phase.)
(Detected
when the
main power
supply was
turned ON.)
method for three-phase
SERVOPACK) to 1 (single-
phase power supply).
parameter setting.
power supply.
A SERVOPACK fault
occurred.
--
Turn the power supply OFF and then
ON again. If the alarm still occurs,
the SERVOPACK may be faulty.
Replace the SERVOPACK.
CPF00
Digital
Operator
Transmission
Error 1
The contact between the
digital operator and the
SERVOPACK is faulty.
Check the connector
contact.
Insert securely the connector or
replace the cable.
Malfunction caused by noise
interference.
--
Keep the digital operator or the
cable away from noise sources.
CPF01
Digital
Operator
Transmission
Error 2
A digital operator fault
occurred.
--
Disconnect the digital operator and
then re-connect it. If the alarm still
occurs, the digital operator may be
faulty. Replace the digital operator.
A SERVOPACK fault
occurred.
--
Turn the power supply OFF and then
ON again. If the alarm still occurs,
the SERVOPACK may be faulty.
Replace the SERVOPACK.