6.14 ZONE Outputs (FT64 Specification)
6.14.1 ZONE Table and ZONE Signals
6-58
6.14
ZONE Outputs (FT64 Specification)
You can use ZONE signals to output a ZONE number to indicate when the current value is
within a registered zone.
The ZONE signals (/ZONE0 to /ZONE3) are assigned to output signals (/SO1 to /SO5) on CN1.
6.14.1
ZONE Table and ZONE Signals
You can register the desired zones in the ZONE table. The ZONE table consists of settings for
the ZONE numbers (ZONE), ZONE N values (ZONE N), and ZONE P values (ZONE P). You can
register up to 16 zones.
The ZONE numbers identify the registered zones.
ZONE N is the lower limit of the ZONE and ZONE P is the upper limit of the ZONE. The setting
conditions for ZONE N and ZONE P are given in the following table.
The ZONE signals indicate the ZONE number. If the current value is within a zone registered in
the ZONE table, the corresponding ZONE number is output on the ZONE signals.
You can use the ZONE signals as required, e.g., to trigger operations related to positioning.
Note: 1: Signal is ON (active), 0: Signal is OFF (inactive).
Setting Range
Setting Unit
Default Setting
When Enabled
-2,147,483,648 to 2,147,483,647
Pos unit
0
Immediately
ZONE Table
ZONE Signals
ZONE Number
(ID)
ZONE N
[Pos unit]
ZONE P
[Pos unit]
/ZONE3
/ZONE2
/ZONE1
/ZONE0
0
±nnnnnnnnnn
±nnnnnnnnnn
0
0
0
0
1
±nnnnnnnnnn
±nnnnnnnnnn
0
0
0
1
2
±nnnnnnnnnn
±nnnnnnnnnn
0
0
1
0
3
±nnnnnnnnnn
±nnnnnnnnnn
0
0
1
1
4
±nnnnnnnnnn
±nnnnnnnnnn
0
1
0
0
5
±nnnnnnnnnn
±nnnnnnnnnn
0
1
0
1
6
±nnnnnnnnnn
±nnnnnnnnnn
0
1
1
0
7
±nnnnnnnnnn
±nnnnnnnnnn
0
1
1
1
8
±nnnnnnnnnn
±nnnnnnnnnn
1
0
0
0
9
±nnnnnnnnnn
±nnnnnnnnnn
1
0
0
1
10
±nnnnnnnnnn
±nnnnnnnnnn
1
0
1
0
11
±nnnnnnnnnn
±nnnnnnnnnn
1
0
1
1
12
±nnnnnnnnnn
±nnnnnnnnnn
1
1
0
0
13
±nnnnnnnnnn
±nnnnnnnnnn
1
1
0
1
14
±nnnnnnnnnn
±nnnnnnnnnn
1
1
1
0
15
±nnnnnnnnnn
±nnnnnnnnnn
1
1
1
1