5.1 A: Initialization
The initialization group contains parameters associated with initial drive setup, including parameters involving the display
language, access levels, initialization, and password.
u
A1: Initialization
n
A1-00: Language Selection
Selects the display language for the digital operator.
Note:
This parameter is not reset when the drive is initialized using parameter A1-03.
No.
Parameter Name
Setting Range
Default
A1-00
Language Selection
0 to 7
0
Setting 0: English
Setting 1: Japanese
Setting 2: German
Setting 3: French
Setting 4: Italian
Setting 5: Spanish
Setting 6: Portuguese
Setting 7: Chinese
n
A1-01: Access Level Selection
Allows or restricts access to drive parameters.
No.
Parameter Name
Setting Range
Default
A1-01
Access Level Selection
0 to 2
2
Setting 0: Operation only
Allows access and programming of parameters A1-01, A1-04, and Drive Mode.
Allows access to all U monitor parameters.
Does not allow access to Verify Mode, Setup Mode, or Auto-Tuning Mode.
Setting 1: User Parameters
Allows access and programming of parameters A1-00, A1-01, A1-04, and Drive Mode.
Allows access to all U monitor parameters.
Allows access to parameters set in A2-01 to A2-32 in Setup Mode.
Does not allow access to Verify Mode or Auto-Tuning Mode.
Setting 2: Advanced Access Level (A) and Setup Access Level (S)
Allows access and programming of all parameters.
Notes on Parameter Access
• If the drive parameters are password protected by A1-04 and A1-05, parameters A1-01 through A1-03, A1-06, A1-07, and
A2-01 through A2-32 cannot be modified.
• If a digital input terminal programmed for “Program lockout” (H1-
oo
= 1B) is enabled, parameter values cannot be
modified, even if A1-01 is set to 1 or 2.
• If parameters are changed via serial communication, it will not be possible to edit or change parameter settings with the
digital operator until an Enter command is issued to the drive from the serial communication.
5.1 A: Initialization
142
YASKAWA SIEP YAIP1U 01C AC Drive - P1000 Technical Manual