![YASKAWA P1000 Quick Start Manual Download Page 102](http://html1.mh-extra.com/html/yaskawa/p1000/p1000_quick-start-manual_3559550102.webp)
d1-04
d1-05
d1-06
d1-07
d1-17
d1-12
d1-13
d1-14
d1-15
d1-16
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
FWD (REV) Run/Stop
Multi-step Speed Ref. 2
Multi-step Speed Ref. 3
Jog Reference
Time
Multi-step Speed Ref. 1
Multi-step Speed Ref. 4
Frequency
reference
d1-01
(A1)
d1-02
(A2)
d1-03
(A3)
Figure 4.17 Preset Reference Timing Diagram
n
E1-01: Input Voltage Setting
Adjusts the levels of some protective features of the drive (overvoltage, Stall Prevention, etc.). Set this parameter to the nominal
voltage of the AC power supply.
NOTICE:
Set parameter E1-01 to match the input voltage of the drive. Drive input voltage (not motor voltage) must be set in E1-01 for the
protective features to function properly. Failure to set the correct drive input voltage will result in improper drive operation.
No.
Parameter Name
Setting Range
Default
E1-01
Input Voltage Setting
E1-01 Related Values
The input voltage setting determines the overvoltage and undervoltage detection levels, the operation levels of the braking
transistor, the KEB function, and the overvoltage suppression function.
Voltage Setting Value of
E1-01
ov Detection Level/Dynamic
Braking Transistor Detection
Level
(Approximate Values)
Uv Detection Level
(L2-05)
Desired DC Bus Voltage
during KEB (L2-11)
ov Suppression /
Stall Prevention Level
(L3-17)
200 V
Class
All settings
410 V / 394 V
190 V
260 V
375 V
400 V
Class
setting
≥
400 V
820 V / 788 V
380 V
500 V
750 V
setting < 400 V
820 V / 788 V
350 V
460 V
750 V
600 V
Class
All settings
1178 V / 1132 V
475 V
635 V
930 V
manual TOBPC72060000 or TOBPC72060001.
4.6 Basic Drive Setup Adjustments
102
YASKAWA ELECTRIC TOEP YAIP1U 01B YASKAWA AC Drive - P1000 Quick Start Guide