Para
me
te
r Lis
t
A
L6: Overtorque Detection
Use L6 parameters to configure overtorque detection.
L6-01
Torque Detection
Selection 1
Selects the overtorque/undertorque operation.
overtorque and undertorque are determined by
the settings in parameters L6-02 and L6-03.
The multi-function output settings (H2-
=
B and 17) are also active if programmed.
0: Disabled
1: OL3 at Speed Agree - Alarm (overtorque
detection only active during Speed Agree and
operation continues after detection).
2: OL3 at RUN - Alarm (overtorque detection is
always active and operation continues after
detection).
3: OL3 at Speed Agree - Fault (overtorque
detection only active during Speed Agree and
drive output will shut down on an OL3 fault).
4: OL3 at RUN - Fault (overtorque detection is
always active and drive output will shut down
on an OL3 fault).
5: UL3 at Speed Agree - Alarm (undertorque
detection is only active during Speed Agree and
operation continues after detection).
6: UL3 at RUN - Alarm (undertorque detection
is always active and operation continues after
detection).
7: UL3 at Speed Agree - Fault (undertorque
detection only active during Speed Agree and
drive output will shut down on an OL3 fault).
8: UL3 at RUN - Fault (undertorque detection is
always active and drive output will shut down
on an OL3 fault).
0 to 8
0
A A A
4A1
L6-02
Torque Detection
Level 1
Sets the overtorque/undertorque detection level.
100% is equal to the motor rated current in V/f
Control and the motor rated torque in Open
Loop Vector Control.
0 to 300 150% A A A
4A2
L6-03
Torque Detection
Time 1
Sets the length of time an overtorque/
undertorque condition must exist before Torque
Detection 1 is triggered.
0.0 to
10.0
0.1 s A A A
4A3
No.
Name
Description
Range Def.
Control
Mode
Addr.
Hex
Pg.