YASKAWA AC Drive L1000V Technical Manual
5.6 F: Simple FeedbackSettings
5.6
F: Simple FeedbackSettings
u
F1: Encoder/PG Feedback Settings
The F1 parameters are used to set the drive up for single channel simlpe closed loop operation using the pulse train input.
n
F1-02, F1-14: PG Open (PGo) Circuit Operation Selection, Detection Time
A PGo fault is triggered if the drive receives no pulse signal for longer than the time set in F1-14. Set the stopping
method for a PGo fault in parameter F1-02.
Parameter F1-02 Settings:
Setting 0: Ramp to stop (uses the deceleration ramp set to C1-02)
Setting 1: Coast to stop
Setting 2: Fast Stop (uses the Fast Stop ramp set to C1-09)
Setting 3: Alarm only
Note:
Due to potential damage to motor and machinery, the “Alarm only” setting should be used only under special circumstances.
n
F1-03, F1-08, F1-09: Overspeed (oS) Operation Selection, Detection Level, Delay Time
An oS fault is triggered when the speed feedback exceeds the value set in F1-08 for longer than the time set in F1-09. Set
the stopping method for an oS fault in parameter F1-03.
Parameter F1-03 Settings:
Setting 0: Ramp to stop (uses the deceleration ramp set to C1-02)
Setting 1: Coast to stop
Setting 2: Fast Stop (uses the Fast Stop ramp set to C1-09)
Setting 3: Alarm only
Note:
Due to potential damage to motor and machinery, refrain from using the “Alarm only” setting except under special
circumstances.
n
F1-04, F1-10, F1-11: Operation at Speed Deviation (dEv), Detection Level, Delay Time
A speed deviation error (dEv) is triggered when the difference between the speed reference and the speed feedback
exceeds the value set in F1-10 for longer than the time set in F1-11. The stopping method when a speed deviation fault
occurs can be selected in parameter F1-04.
Settings for Parameter F1-04:
Setting 0: Ramp to stop (uses the deceleration ramp set to C1-02)
Setting 1: Coast to stop
Setting 2: Fast Stop (uses the Fast Stop ramp set to C1-09)
Setting 3: Alarm only (drive continues operating while “dEv” flashes on the screen)
No.
Parameter Name
Setting Range
Default
F1-02
Operation Selection at PG Open Circuit (PGo)
0 to 3
1
F1-14
PG Open-Circuit Detection Time
0.0 to 10.0 s
2.0 s
No.
Parameter Name
Setting Range
Default
F1-03
Operation Selection at Overspeed (oS)
0 to 3
1
F1-08
Overspeed Detection Level
0 to 120%
115%
F1-09
Overspeed Detection Delay Time
0.0 to 2.0 s
0.0 s
No.
Parameter Name
Setting Range
Default
F1-04
Operation Selection at Deviation
0 to 3
3
F1-10
Excessive Speed Deviation Detection Level
0 to 50%
10%
F1-11
Excessive Speed Deviation Detection Delay Time
0.0 to 10.0 s
0.5 s
Summary of Contents for Lift Inverter L1000V
Page 4: ...4 YASKAWA EUROPE SIEP YASKAWA AC Drive L1000V Technical Manual...
Page 28: ...1 4 Component Names 28 YASKAWA EUROPE SIEP YASKAWA AC Drive L1000V Technical Manual...
Page 62: ...3 10 Wiring Checklist 62 YASKAWA EUROPE SIEP YASKAWA AC Drive L1000V Technical Manual...
Page 162: ...5 12 U Monitor Parameters 162 YASKAWA EUROPE SIEP YASKAWA AC Drive L1000V Technical Manual...
Page 279: ...8 YASKAWA EUROPE SIEP YASKAWA AC Drive L1000V Technical Manual...
Page 281: ...10 YASKAWA ELECTRIC SIEP C710616 33C YASKAWA AC Drive L1000A Technical Manual...