5.1 A: Initialization
YASKAWA EUROPE SIEP
YASKAWA AC Drive L1000V Technical Manual
105
P
a
ra
me
te
r D
e
ta
ils
5
Note:
Parameter settings can be edited after entering the correct password. Performing a 2-wire initialization resets the password to
“0000”. Reenter the password to parameter A1-05 after drive initialization.
u
A2: User Parameters
n
A2-01 to A2-32: User Parameters 1 to 32
The user can select up to 32 parameters and assign them to parameters A2-01 through A2-32 to provide quicker access
by eliminating the need to scroll through multiple menus. The User Parameter list can also save the most recently edited
parameters.
Saving User Parameters
To save specific parameters to A2-01 through A2-32, set parameter A1-01 to 2 to allow access to all parameters, then
enter the parameter number to one of the A2-oo parameters to assign it to the list of User Parameters. Finally, set A1-01
to 1 to restrict access so users can only set and refer to the parameters saved as User Parameters.
n
A2-33: User Parameter Automatic Selection
Determines whether recently edited parameters are saved to the second half of the User Parameters (A2-17 to A2-32) for
quicker access.
Setting 0: Do not save list of recently viewed parameters.
Set A2-33 to 0 to manually select the parameters listed in the User Parameter group.
Setting 1: Save history of recently viewed parameters.
Set A2-33 to 1 to automatically save recently edited parameters to A2-17 through A2-32. A total of 16 parameters are
saved with the most recently edited parameter set to A2-17, the second most recently to A2-18, and so on. Access the
User Parameters using the Setup Mode of the digital operator.
6.
Drive returns to the parameter display.
7.
Press
and scroll to A1-01.
8.
Press
to display the value set to A1-01. If the first “0” blinks, parameter settings are unlocked.
9.
Use ,
and
to
change the value if desired.
10.
Press
to save the setting, or press
to return to the previous display without saving changes.
11.
The display automatically returns to the parameter display.
No.
Parameter Name
Setting Range
Default
A2-01 to A2-32
User Parameters 1 to 32
A1-00 to o4-13
Determined by A1-02
No.
Parameter Name
Setting Range
Default
A2-33
User Parameter Automatic Selection
0 or 1
1
Step
Display/Result
Summary of Contents for Lift Inverter L1000V
Page 4: ...4 YASKAWA EUROPE SIEP YASKAWA AC Drive L1000V Technical Manual...
Page 28: ...1 4 Component Names 28 YASKAWA EUROPE SIEP YASKAWA AC Drive L1000V Technical Manual...
Page 62: ...3 10 Wiring Checklist 62 YASKAWA EUROPE SIEP YASKAWA AC Drive L1000V Technical Manual...
Page 162: ...5 12 U Monitor Parameters 162 YASKAWA EUROPE SIEP YASKAWA AC Drive L1000V Technical Manual...
Page 279: ...8 YASKAWA EUROPE SIEP YASKAWA AC Drive L1000V Technical Manual...
Page 281: ...10 YASKAWA ELECTRIC SIEP C710616 33C YASKAWA AC Drive L1000A Technical Manual...