6.1 MEMOBUS/Modbus Communications
YASKAWA
SIEPYEULA5001C LA500 Technical Manual
163
Table 6.19 MEMOBUS/Modbus Communications Error Codes
Error Code
(Hex.)
Name
Cause
01
Function Code Error
The PLC set a function code that was not 03, 08, or 10 (Hex.)
02
Register Number Error
•
The register number that is trying to access is not registered.
•
A starting number that was not 0001 or 0002 (Hex.) was set when broadcasting.
03
Bit Count Error
•
Read and write data quantities are more than the 1 to 16 range. (Command message data quantity is disabled.)
•
The data that was read from non-consecutive holding registers contained more than 120 bytes.
•
The data to be written to non-consecutive holding registers contained more than 60 bytes.
•
In the write mode, the number of bytes in the message is not the number of data × 2.
21
Data Setting Error
•
Writing control data or parameters made the settings go out of the permitted setting range.
•
A parameter setting error occurred when writing a parameter.
22
Write Mode Error
•
Tried to write a disabled parameter during run.
•
When there was a
CPF06 [Control Circuit Error]
, the master tried to write a parameter other than one of these:
–
A1-00 [Language Selection]
–
A1-01 [Access Level Selection]
–
A1-02 [Control Method Selection]
–
A1-03 [Initialize Parameters]
–
A1-04 [Password]
–
A1-05 [Password Setting]
–
E1-03 [V/f Pattern Selection]
–
o2-04 [Drive Model (KVA) Selection]
•
Writes the read-only data.
23
DC Bus Undervoltage
Write Error
During
Uv [DC Bus Undervoltage]
, a
Uv
write disabled parameter was written.
24
Error Writing Data During
Parameter Processing
Tried to write a parameter from the master during parameter processing on the drive side.
25
Writing into EEPROM
Disabled
Writing into EEPROM write is disabled, but EEPROM write was executed from MEMOBUS/Modbus communications. When
this error occurs, the keypad shows a message and the drive continues operation.
■
No Response from Slave
The slave ignores the command message from the master and will not send a response message in these
conditions:
•
When a communications error (overrun, framing, parity, CRC-16) is detected in the command message.
•
When the slave address in the command message and the slave address for the drive side do not agree (Use
H5-
01 [Drive Node Address]
to set the slave address of the drive)
•
When the time interval between the data of which the message is composed is longer than 24 bits
•
When the data length for the command message is not accurate
Note:
•
If the keypad shows
CALL [Serial Comm Transmission Error]
, refer to
“
Troubleshooting
”
to remove the cause of the error, and try to
do communications again. If the keypad does not show
CALL
, check
U1-19 [MEMOBUS/Modbus Error Code]
for the error and error
type.
•
If you execute the write function code when the slave address in the command message is 00 (Hex.), all of the slaves will execute the
write command, but they will not send response messages to the master.
Summary of Contents for LA500
Page 2: ...This Page Intentionally Blank 2 YASKAWA SIEPYEULA5001C LA500 Technical Manual...
Page 10: ...10 YASKAWA SIEPYEULA5001C LA500 Technical Manual...
Page 18: ...i 3 Glossary 18 YASKAWA SIEPYEULA5001C LA500 Technical Manual...
Page 74: ...3 14 Wiring Checklist 74 YASKAWA SIEPYEULA5001C LA500 Technical Manual...
Page 164: ...6 1 MEMOBUS Modbus Communications 164 YASKAWA SIEPYEULA5001C LA500 Technical Manual...
Page 202: ...7 10 Troubleshooting Without Fault Display 202 YASKAWA SIEPYEULA5001C LA500 Technical Manual...
Page 218: ...8 6 Storage Guidelines 218 YASKAWA SIEPYEULA5001C LA500 Technical Manual...
Page 234: ...10 6 Peripheral Devices and Options 234 YASKAWA SIEPYEULA5001C LA500 Technical Manual...
Page 375: ...YASKAWA SIEPYEULA5001C LA500 Technical Manual 375...