B.3 Parameter Table
No.(Addr.)
Name
Description
Setting
Page
d1-28
(2CAH)
Leveling Speed Detection Level
U
u
sed when d1-1
ses the leveling
8 = 0 or 3. If the speed reference selected is lower than d1-28, then the drive
speed as the speed reference.
Default: 0.0%
Min: 0.0%
Max: 100.0%
156
d1-29
(2CBH)
Inspection Speed Detection Level
U
e
sed when d1-1
qual to d1-29, t
ШШШЯШШШЯШШ
I
8 = 0 or 3. If the speed reference selected is higher than d1-28 but lower or
hen the drive uses inspection speed as the speed reference.
Default: 0.0%
Min: 0.0%
Max: 100.0%
156
<6> Setting ranges and defaults vary by the setting units determined by param eter o1-03.
Refer to
Defaults a n d S etting Ranges by D isplay U n it Selection (o1-03) on page 365
■ d6: Field Forcing
No.(Addr.)
Name
Description
Setting
Page
d6-03
(2A 2H )
Field Forcing Selection
f
l
V/f
rn^rn
c lv /p m j
i
0: Disabled
1: Enabled
Default: 0
Min: 0
Max: 1
156
d6-06
(2A 5H )
Field Forcing Limit
Sets the upper limit o f the excitation current command during magnetic field forcing. A setting
o f 100% is equal to motor no-load current. Disabled only during DC Injection Braking.
Default: 400%
Min: 100%
Max: 400%
156
♦ E: Motor Parameters
■ E1: V/f Pattern
No.(Addr.)
Name
E1-01
(300H)
Input Voltage Setting
E1-03
(302H)
V /f Pattern Selection
E1-04
(303H)
Maximum Output Frequency
E1-05
(304H)
Maximum Voltage
E1-06
(305H)
Base Frequency
E1-07
(306H)
Middle Output Frequency
E1-08
(307H)
Middle Output Frequency Voltage
E1-09
(308H)
Minimum Output Frequency
E1-10
(309H)
Minimum Output Frequency
Voltage
E1-11
(30A H )
<11>
Middle Output Frequency 2
E1-12
(30B H )
<11>
Middle Output Frequency Voltage 2
E1-13
(30CH)
Base Voltage
Description
Setting
Page
Default: 200 V <9>
Min: 155 V
Max: 255 V <9>
1 5 7
Default: F
Min: -
Max: F
1 5 7
Default: <5>
Min: <33>
Max: 120.0 Hz
1 5 7
Default: 190.0 V <9>
Min: 0.0 V
Max: 255.0 V <9>
1 5 7
Default: <5>
Min: 0.0 Hz
Max: 120.0 Hz
1 5 7
Default: 3.0 Hz
Min: 0.0 Hz
Max: 120.0 Hz
1 5 7
Default: <2> <9>
Min: 0.0 V
Max: 255.0 V <9>
1 5 7
Default: <5>
Min: 0.0 Hz
Max: 120.0 Hz
1 5 7
Default: <2> <9>
Min: 0.0 V
Max: 255.0 V <9>
1 5 7
Default: 0.0 Hz
Min: 0.0 Hz
Max: 120.0 Hz
1 5 7
Default: 0.0 V <9>
Min: 0.0 V
Max: 255.0 V <9>
1 5 7
Default: 0.0 V
<9> <13>
Min: 0.0 V
Max: 255.0 V <9>
1 5 7
This parameter must be set to the power supply voltage.
W A R N I N G !
Electrical Shock Hazard. Drive input voltage (not motor voltage) must be set in
E1-01 for the protective features o f the drive to function properly. Failure to do so may result in
equipment damage and/or death or personal injury.
F: Custom V/f, E 1-04 through E1-13 settings define the V /f pattern
To set linear V /f characteristics, set the same values for E 1-07 and E1-09. In this case, the
setting for E1-08 w ill be disregarded. Ensure that the four frequencies are set according to these
rules:
E 1-09 < E 1-07 < E 1-06 < E 1 -1 1 < E 1-04
N ote that if E1-11 = 0, then both E1-11 and E 1-12 are disabled, and the above conditions do not
apply.
O u t p u t V o lta g e (V )
F re q u e n c y (H z )
N o t e :
Some parameters may not be available depending on the control mode.
• E 1-07, E1-08 and E-10 are available only in the V /f control and Open Loop Vector control
modes.
• E1-11, E1-12 and E-13 are available only in the V /f control and C losed Loop Vector control
modes.
V/f
CLV
CLV/PM
<2> D efault setting is dependent on the control mode (A1-02) and the drive model (o2-04).
<5> D efault setting is determined by the control mode (A1-02).
<9> Values shown here are for 200 V class drives. Double the value when using a 400 V class drive.
<11> Param eter is ignored when E1-11 and E1-12 are set to 0.0.
<13> Auto-Tuning will set E1-13 to the same value as E1-05.
<33> Setting range depends on the type o f m otor being used. CLV allows a setting range o f 10.0 to 120.0 H z, w hile CLV/PM allows a setting range
o f 4.0 to 120.0 Hz.
330
YASKAWA ELECTRIC SIEP C710616 33D YASKAWA AC Drive L1000A Technical Manual