TOEPC710616134G AC Drive L1000A Technical Manual Addendum
21
Speed Mode Bits
DCP Name of Speed Mode
L1000A Standard Speed
Designation
Related L1000A Parameter
L1000A DCP Designation
G4
VI
Inspection
d1-24
VI Speed
G5
V2
Intermediate 2
d1-03
V2 Speed
G6
V3
Intermediate 1
d1-02
V3 Speed
G7
V4
Fast
d1-01
V4 Speed
G8
V5
Intermediate 6
d1-07
V5 Speed
G9
V6
Intermediate 5
d1-06
V6 Speed
G10
V7
Intermediate 4
d1-05
V7 Speed
Speed modes V7, V6, V5, V2, and V1 are not available with DCP4.
◆
DCP Slave Messages from Drive Controller to Lift Controller
■
Status Byte
Process Data
Communication Data
Checksum
1
2
3
4
5
6
Status Byte
(S7 ... S0)
Data Byte 1
Data Byte 2
Communication Byte 1
Communication Byte 2
Checksum
The first byte of the message is called status byte. It contains the following information:
Bit S0 : Drive controller ready
DCP3 and DCP4:
The drive controller is ready for the next run. This status bit is similar to the terminal "Drive controller ready" at
the lift controller.
0 : Drive controller is not ready to travel
1 : Drive controller is ready to travel
Bit S1 : Travel active
DCP3 and DCP4:
The drive controller is currently carrying out a run.
0 : Not in travel
1 : In travel
Bit S2 : Stop switch
DCP3 and DCP4:
The travel can be continued to the next floor. In this case, the lift controller should no longer give any travel
commands while alarms are active.
Bit S3 : Fault active
DCP3 and DCP4:
The drive controller error flag is set. The drive controller has been switched off, the run contactor was closed, and
the brake was applied. Possible causes of the fault include:
•
Over-speed
•
Over-current
•
DC bus over-voltage
•
DC bus under-voltage
•
Motor parameter setting error
•
Power section over-temperature
The command "Drive controller enable" (see command bit B0) must be cleared at this situation. The lift controller
will not travel until the fault has been cleared on the drive side.
Bit S4 : Motor speed below leveling speed (v < 0.3 m/s)
DCP3 and DCP4:
The motor speed has dropped to or below leveling speed. This signal is used for monitoring the re-leveling speed
(v < 0.3 m/s) by the lift controller.
EN
Summary of Contents for L1000A CIMR-LC F Series
Page 1: ...AC Drive L1000A For Lift Applications Technical Manual Addendum Type CIMR LCxFxxxxxxx 913x Web...
Page 98: ...15 Appendix 98 YASKAWA TOEPC710616134G AC Drive L1000A Technical Manual Addendum...
Page 99: ...15 Appendix YASKAWA TOEPC710616134G AC Drive L1000A Technical Manual Addendum 99 EN...
Page 100: ...15 Appendix 100 YASKAWA TOEPC710616134G AC Drive L1000A Technical Manual Addendum...
Page 101: ...15 Appendix YASKAWA TOEPC710616134G AC Drive L1000A Technical Manual Addendum 101 EN...
Page 102: ...15 Appendix 102 YASKAWA TOEPC710616134G AC Drive L1000A Technical Manual Addendum...