B.2 A: Initialization Parameters
Table B.1 Symbols and Icons Used in Parameter Descriptions
Symbol
Description
Parameter can be changed during run.
The A parameter group creates the operating environment for the drive. This includes the parameter Access Level, Motor
Control Method, Password, User Parameters and more.
u
A1: Initialization
No.
(Addr.
Hex)
Name
LCD Display
Description
Values
Page
A1-00
(0100)
Language Selection
Select Language
0: English
1:
(Japanese)
2: Deutsch
3: Fran
ç
ais
4: Italiano
5: Español
6: Portugu
ê
s
7:
0: English
1: Japanese
2: German
3: French
4: Italian
5: Spanish
6: Portuguese
7: Chinese
Default: 0
Range: 0 to 7
A1-01
(0101)
Access Level Selection
Access Level
0: Operation Only
1: User Parameters
2: Advanced Level
3: Lock parameters
0: View and set A1-01 and A1-04. U
o
-
oo
parameters can also
be viewed.
1: User Parameters (access to parameters selected by the user,
A2-01 to A2-32)
2: Advanced Access (access to view and set all parameters)
3: Lock parameters
Default: 2
Range: 0 to 3
A1-03
(0103) Initialize Parameters
Init Parameters
0: No Initialize
1110: User Initialize
2220: 2-Wire Initial
3330: 3-Wire Initial
5550: Term->Cntrl Int
6008: Pressure Control
6009: Pump down level
7770: General purpose
7771: Sub Mtr GP
Operation
0: No initialization
1110: User Initialize (parameter values must be stored using
parameter o2-03)
2220: 2-Wire initialization
3330: 3-Wire initialization
5550: Terminal->Control Initialize
6008: Pressure Control
6009: Pump down level
7770: General purpose
7771: Submersible motor GP operation
Default: 0
Range: 0 to 5550;
6008, 6009, 7770,
7771
A1-04
(0104) Password
Enter Password
When the value set into A1-04 does not match the value set into
A1-05, parameters A1-01 through A1-03 and A2-01 through A2-33
cannot be changed.
Default: 0000
Min.: 0000
Max.: 9999
A1-05
(0105) Password Setting
Select Password
A1-06
(0127) Application Preset
Application Sel
0: Pressure Control
1: General Purpose
2: Sub Mtr GP
Operation
8: Pressure Control
9: Pump Down Level
0: Pressure control
1: General purpose
2: Submersible motor GP operation
8: Pressure control
9: Pump down level
Note:
This parameter is not settable. It is used as a
monitor only.
Default: 0
Range: 0 to 2: 8, 9
<1> Parameter setting value is not reset to the default value when the drive is initialized.
<2> Default setting value is dependent on the Initialization parameter A1-03.
u
A2: User Parameters
No.
(Addr.
Hex)
Name
LCD Display
Description
Values
Page
A2-01 to
A2-32
(0106 to
0125)
User Parameters 1 to 32
User Param 1 - 32
Recently edited parameters are listed here. The user can also select
parameters to appear here for quicker access.
Range: b1-01 to
S6-02
A2-33
(0126)
User Parameter
Automatic Selection
User Parms Sel
0: Disabled
1: Enabled
0: A2-01 to A2-32 are reserved for the user to create a list of User
Parameters.
1: Save history of recently viewed parameters. Recently edited
parameters will be saved to A2-17 through A2-32 for quicker
access.
Default: 0
Range: 0, 1
–
<1> Default setting value is dependent on the Initialization parameter A1-03.
B.2 A: Initialization Parameters
YASKAWA
TOEP YAIQPM 03B YASKAWA AC Drive - iQpump Micro User Manual
319
B
Parameter List