A.4 Drive Derating Data
The drive can be operated at above the rated temperature, altitude, and default carrier frequency by derating the drive capacity.
u
Single-Phase Derating
iQpump Micro drives are compatible for use with both three-phase and single-phase input power supplies. The drive output
to the motor is always three-phase, regardless of number of input phases.
Output capacity to the motor is derated when using single-phase input power and the drive firmware includes protection for
single-phase input applications. This protection is enabled by default. Disabling this protection for single-phase input
applications can void warranty and result in premature failure.
Selection of larger models always results in greater output capacity to the motor when supplying the drive with three-phase
input power. However, the selection of larger models does not always yield greater output capacity when using the drive with
single-phase input power.
Several factors affect the amount of derated drive output capacity when single-phase input power is supplied to the drive:
• Single-phase input voltage level
• Motor voltage rating
• Amount of input impedance.
The tables in this section assist in model selection by considering factors that affect the amount of derating in single-phase
input power applications.
n
Single-Phase Input Sizing
The rated output current listed in the tables allows for a 120% overload for 60 seconds. Contact Yaskawa if assistance is needed
in selecting drive models with higher overload requirements. Adding more impedance than is specified will degrade
performance.
Table A.9 240 V Single-Phase Input (-5% to +10%)
Drive Model
Without Input Reactor
With Input Reactor
Rated Input
Current (A)
Rated
Output
Current (A)
Max
Applicable
Motor (HP)
Yaskawa Reactor Part
Number
Rated Input
Current (A)
Rated
Output
Current (A)
Max
Applicable
Motor (HP)
2V0006
7.3
4.9
1.0
URX000303
7.3
4.9
1.0
2V0010
10.8
6.8
1.5
URX000307
10.8
6.8
1.5
2V0012
13.9
7.5
2.0
URX000311
13.9
7.5
2.0
2V0020
24.0
9.7
2.0
URX000319
24.0
12.3
3.0
2V0030
37.0
7.5
2.0
URX000326
37.0
15.2
3.0
2V0040
52.0
16.7
5.0
URX000329
52.0
21.0
5.0
2V0056
68.0
23.4
5.0
URX000335
68.0
27.7
7.5
2V0069
80.0
25.8
7.5
URX000335
80.0
30.8
10.0
Table A.10 480 V Single-Phase Input (-5% to +10%)
Drive Model
Without Input Reactor
With Input Reactor
Rated Input
Current (A)
Rated
Output
Current (A)
Max
Applicable
Motor (HP)
Yaskawa Reactor Part
Number
Rated Input
Current (A)
Rated
Output
Current (A)
Max
Applicable
Motor (HP)
4V0002
2.1
1.3
0.5
URX000292
2.1
1.7
0.5
4V0004
4.3
2.4
1.0
URX000300
4.3
2.8
1.0
4V0005
5.9
3.5
1.5
URX000304
5.9
3.9
2.0
4V0007
8.1
3.5
1.5
URX000309
8.1
5.4
2.0
4V0009
9.4
5.1
2.0
URX000308
9.4
5.5
3.0
4V0011
14.0
5.5
3.0
URX000312
14.0
7.5
3.0
4V0018
20.0
4.5
2.0
URX000316
20.0
8.7
5.0
4V0023
24.0
5.5
3.0
URX000320
24.0
10.5
5.0
4V0031
38.0
7.9
3.0
URX000327
38.0
13.5
7.5
4V0038
44.0
11.3
5.0
URX000327
44.0
16.1
10.0
A.4 Drive Derating Data
314
YASKAWA
TOEP YAIQPM 03B YASKAWA AC Drive - iQpump Micro User Manual