250
YASKAWA
SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
■
E1-08: Mid Point A Voltage
No.
(Hex.)
Name
Description
Default
(Range)
E1-08
(0307)
Mid Point A Voltage
Sets a middle output voltage for the V/f pattern.
Determined by o2-04
(208/240 V: 0.0 - 255.0 V,
480 V: 0.0 - 510.0 V)
Note:
Default setting is determined by
o2-04 [Drive Model Selection]
.
■
E1-09: Minimum Output Frequency
No.
(Hex.)
Name
Description
Default
(Range)
E1-09
(0308)
Minimum Output Frequency Sets the minimum output frequency for the V/f pattern.
1.5 Hz
(Determined by E1-04)
■
E1-10: Minimum Output Voltage
No.
(Hex.)
Name
Description
Default
(Range)
E1-10
(0309)
Minimum Output Voltage
Sets the minimum output voltage for the V/f pattern.
10.2 V
(208/240 V: 0.0 - 255.0 V,
480 V: 0.0 - 510.0 V)
■
E1-11: Mid Point B Frequency
No.
(Hex.)
Name
Description
Default
(Range)
E1-11
(030A)
Expert
Mid Point B Frequency
Sets a middle output frequency for the V/f pattern.
0.0 Hz
(0.0 - E1-04)
Note:
Set this parameter to
0.0
to disable the function.
■
E1-12: Mid Point B Voltage
No.
(Hex.)
Name
Description
Default
(Range)
E1-12
(030B)
Expert
Mid Point B Voltage
Sets a middle point voltage for the V/f pattern.
0.0 V
(208/240 V: 0.0 - 255.0 V,
480 V: 0.0 - 510.0 V)
Note:
Set this parameter to 0.0 to disable the function.
■
E1-13: Base Voltage
No.
(Hex.)
Name
Description
Default
(Range)
E1-13
(030C)
Expert
Base Voltage
Sets the base voltage for the V/f pattern.
0.0 V
(208/240 V: 0.0 - 255.0 V,
480 V: 0.0 - 510.0 V)
Note:
•
After Auto-Tuning, the value of
E1-13
=
E1-05 [Maximum Output Voltage]
.
•
When
E1-13 = 0.0
, use the value of
E1-05
to control the voltage.
◆
E2: Motor Parameters
E2 parameters [Motor Parameters]
set induction motor data. To switch drive operation from one motor to another
motor, configure the first motor (motor 1).
Summary of Contents for HV600
Page 12: ...12 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 74: ...Page Intentionally Blank...
Page 76: ...Page Intentionally Blank...
Page 454: ...5 14 Z Bypass Parameters 454 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 590: ...8 6 Storage Guidelines 590 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 780: ...11 3 European Standards 780 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...