T1-11: Motor Iron Loss
No.
(Hex.)
Name
Description
Default
(Range)
T1-11
(070B)
Motor Iron Loss
Sets the iron loss for calculating the energy-saving coefficient.
Determined by E2-11 or E4-
11
(0 - 65535 W)
Note:
The default setting is different for different motor codes and motor parameter settings.
The value shown is the
E2-10 [Motor Iron Loss]
or
E4-10 [Motor 2 Iron Loss]
for the motor output set in
T1-02
[Motor Rated Power]
. If the motor test report is available, enter the motor iron loss value to
T1-11
.
◆
T2: PM Motor Auto-Tuning
T2 parameters
set the Auto-Tuning input data for PM motor tuning.
Note:
The drive automatically sets these PM motor parameters:
•
E1-xx [V/f Pattern for Motor 1]
•
E5-xx [V/f Pattern for Motor 1]
■
T2-01: PM Auto-Tuning Selection
No.
(Hex.)
Name
Description
Default
(Range)
T2-01
(0750)
PM Auto-Tuning Selection
Sets the type of Auto-Tuning for PM motors.
0
(0 - 5)
Note:
Yaskawa recommends Rotational (Ld, Lq, R, back-EMF) for specialized motors. Rotational Auto-Tuning rotates the motor to measure the
actual induction voltage constants for more accurate control than Stationary Auto-Tuning.
0 : Manual Entry w/ Motor Data Sheet
1 : Stationary (Ld, Lq, R)
2 : Stationary (R Only)
4 : Rotational (Ld, Lq, R, back-EMF)
5 : High Frequency Injection
■
T2-02: PM Motor Code Selection
No.
(Hex.)
Name
Description
Default
(Range)
T2-02
(0751)
PM Motor Code Selection
Enter the PM motor code as specified by the rotation speed and motor output.
FFFF
(0000 - FFFF)
Enter the motor code in this parameter to automatically set parameters
T2-03 to T2-14
. When you are operating a
specialized motor or a non-Yaskawa motor, set this parameter to
FFFF
and enter the data from the motor nameplate
or the motor test report.
You can only enter the permitted PM motor codes. Different drive control methods will accept different PM motor
codes.
■
T2-03: PM Motor Type
No.
(Hex.)
Name
Description
Default
(Range)
T2-03
(0752)
PM Motor Type
Sets the type of PM motor the drive will operate.
1
(0, 1)
0 : IPM motor
IPM motors have magnets in the rotor, and Ld ≠ Lq.
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV