bit 7 : dWF3 - DriveWorksEZ Fault 3
bit 8 : dWFL - DriveWorksEZ Fault
bit 9 : MSL - Net Master Lost
bit 10 : VLTS - Thermostat Fault
bit 11 to 15 : Reserved
Note:
The drive sets the bits in Hex.
■
S6-16: EMOVR Customer Safety Mode
No.
(Hex.)
Name
Description
Default
(Range)
S6-16
(3247)
EMOVR Customer Safety
Mode
Sets the status for the customer safety input (when programmed) that must occur for Emergency
Override to function.
0
(0 - 2)
0 : Customer Safety Ignored
1 : EMOVRun Only When Safety OK
2 : EMOVRun Only When Safety NOT OK
Note:
You must set a customer safety to a Digital Input for this parameter to have an effect.
■
S6-17: EMOVR BAS Interlock Mode
No.
(Hex.)
Name
Description
Default
(Range)
S6-17
(3248)
EMOVR BAS Interlock
Mode
Sets the status for the BAS Interlock input (when programmed) that must occur for Emergency
Override to function.
0
(0 - 2)
0 : BAS Interlock Ignored
1 : EMOVRun Only When Interlock OK
2 : EMOVRun When Interlock NOT OK
Note:
Parameter has no effect if BAS Interlock is not programmed to a Digital Input.
■
S6-23: OV2 Detect Time
No.
(Hex.)
Name
Description
Default
(Range)
S6-23
(324E)
OV2 Detect Time
Sets the detection time of
ov2 [DC Bus Overvoltage 2]
in 0.1 s increments.
10.0 s
(0.0 - 1200.0 s)
Note:
Set this parameter to 0.0 s to disable
ov2
detection.
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV