2.11 o: Keypad-Related Settings
422
YASKAWA
TOEPYAIHV6002A HV600 Drive Programming
Note:
The maintenance period changes for different operating environments.
■
o4-07: Softcharge Relay Maintenance Set
No.
(Hex.)
Name
Description
Default
(Range)
o4-07
(0523)
Softcharge Relay
Maintenance Set
Sets the
U4-06 [PreChargeRelayMainte]
monitor value.
0%
(0 - 150%)
When you replace a drive, set
o4-07 = 0
to reset
U4-06
. When the
o4-07
setting changes, the count of
U4-06
starts
again as specified by the setting of
o4-07
. After you complete the configuration,
o4-07
automatically resets to
0
.
Note:
The maintenance period changes for different operating environments.
■
o4-09: IGBT Maintenance Setting
No.
(Hex.)
Name
Description
Default
(Range)
o4-09
(0525)
IGBT Maintenance Setting
Sets the
U4-07 [IGBT Maintenance]
monitor value.
0%
(0 - 150%)
When you replace a drive, set
o4-09 = 0
to reset
U4-07
. When the
o4-09
setting changes, the count of
U4-07
starts
again as specified by the setting of
o4-09
. After you complete the configuration,
o4-09
automatically resets to
0
.
Note:
The maintenance period changes for different operating environments.
■
o4-11: Fault Trace/History Init (U2/U3)
No.
(Hex.)
Name
Description
Default
(Range)
o4-11
(0510)
Fault Trace/History Init (U2/
U3)
Resets the records of Monitors
U2-xx [Fault Trace]
and
U3-xx [Fault History]
.
0
(0, 1)
Note:
When you initialize the drive with
A1-03 [Initialize Parameters]
, the drive will not reset the records for
U2-xx
and
U3-xx
.
0 : Disabled
Keeps the records of Monitors
U2-xx
and
U3-xx
.
1 : Enabled
Resets the records for Monitors
U2-xx
and
U3-xx
. After the reset, the drive automatically resets
o4-11
to
0
.
■
o4-12: kWh Monitor Initialization
No.
(Hex.)
Name
Description
Default
(Range)
o4-12
(0512)
kWh Monitor Initialization
Resets the monitor values for
U4-10 [kWh, Lower 4 Digits]
and
U4-11 [kWh, Upper 5 Digits]
.
0
(0, 1)
Note:
When you initialize the drive with
A1-03 [Initialize Parameters]
, the drive will not reset
U4-10
and
U4-11
.
0 : No Reset
Keeps the monitor values for
U4-10
and
U4-11
.
1 : Reset
Resets the values of
U4-10
and
U4-11
. After the reset, the drive automatically resets
o4-12
to
0
.
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV