2.11 o: Keypad-Related Settings
YASKAWA
TOEPYAIHV6002A HV600 Drive Programming
409
Uses
o1-09 [Freq. Reference Display Units]
,
o1-10 [User Units Maximum Value]
, and
o1-11 [User Units Decimal
Position]
to set the unit of measure. The value of parameter
o1-10
is the value when you remove the decimal point
from the maximum output frequency. Parameter
o1-11
is to the number of digits after the decimal point in the
maximum output frequency.
To display a maximum output frequency of 100.00, set parameters to these values:
•
o1-10 = 10000
•
o1-11 = 2 [User Units Decimal Position = 2 Dec (XXX.XX)]
■
o1-05: LCD Contrast Adjustment
No.
(Hex.)
Name
Description
Default
(Range)
o1-05
(0504)
RUN
LCD Contrast Adjustment
Sets the contrast of the LCD display on the keypad.
5
(0 - 10)
When you decrease the setting value, the contrast of the LCD display decreases. When you increase the setting value,
the contrast increases.
■
o1-09: Freq. Reference Display Units
No.
(Hex.)
Name
Description
Default
(Range)
o1-09
(051C)
Freq. Reference Display
Units
Sets the unit of display for the frequency reference parameters and frequency-related monitors when
o1-03 = 3 [Frequency Display Unit Selection = User Units (o1-09 ~ o1-11)]
.
50
(0 - 50)
0 : “WC: inches of water column
1 : PSI: pounds per square inch
2 : GPM: gallons/min
3 :
°
F: Fahrenheit
4 : ft
3
/min: cubic feet/min
5 : m
3
/h: cubic meters/hour
6 : L/h: liters/hour
7 : L/s: liters/sec
8 : bar: bar
9 : Pa: Pascal
10 :
°
C: Celsius
11 : m: meters
12 : ft: feet
13 : L/min: liters/min
14 : m
3
/min: cubic meters/min
15 : “Hg: Inch Mercury
16 : kPa: kilopascal
48 : %: Percent
49 : Custom(o1-13~15)
50 : None
■
o1-10: User Units Maximum Value
No.
(Hex.)
Name
Description
Default
(Range)
o1-10
(0520)
User Units Maximum Value
Sets the value that the drive shows as the maximum output frequency.
Determined by o1-03
(1 - 60000)
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV