2.11 o: Keypad-Related Settings
408
YASKAWA
TOEPYAIHV6002A HV600 Drive Programming
Keypad Display
Description
When the keypad must show an Information Text and
message at the same time, it will toggle the second and third
lines each 2 s.
When the keypad must show an alarm, Information Text,
and message at the same time, it will toggle the second and
third lines each 2 s.
■
o1-03: Frequency Display Unit Selection
No.
(Hex.)
Name
Description
Default
(Range)
o1-03
(0502)
Frequency Display Unit
Selection
Sets the display units for the frequency reference and output frequency.
0
(0 - 3)
Note:
•
Select the units for these parameters:
–
d1-01 [Reference 1]
to
d1-08 [Reference 8]
,
d1-17 [Jog Reference]
–
U1-01 [Frequency Reference]
–
U1-02 [Output Frequency]
–
U1-05 [Motor Speed]
–
U1-16 [SFS Output Frequency]
–
U4-14 [PeakHold Output Freq]
–
U5-07 [AUTO Mode Freq Ref]
–
U5-08 [HAND Mode Freq Ref]
•
For motor 2, the settings are always
0 [in Hz unit]
.
0 : 0.01Hz units
1 : 0.01% units
The maximum output frequency is 100%.
Note:
Parameter
A1-02 [Control Method Selection]
selects which parameter is the maximum output frequency.
•
A1-02 ≠ 8 [EZOLV]
:
E1-04 [Maximum Output Frequency]
•
A1-02 = 8
:
E9-02 [Motor Max Revolutions]
2 : min
-1
(r/min) unit
The drive uses the maximum output frequency and number of motor poles calculate this value automatically.
Note:
When you set
o1-03 = 2 [r/min]
, make sure that you set the number of motor poles in these parameters:
•
E2-04 [Motor Pole Count]
•
E4-04 [Motor 2 Motor Poles]
•
E5-04 [PM Motor Pole Count]
•
E9-08 [Number of Poles]
3 : User Units (o1-09 -o1-11)
V/f
OLV/PM
OLV/PM
EZOLV