L8-15: Drive oL2 @ Low Speed Protection
No.
(Hex.)
Name
Description
Default
(Range)
L8-15
(04BB)
Drive oL2 @ Low Speed
Protection
Sets the function to decrease drive overload at low speeds to prevent damage to the main circuit
transistor during low speed operation (at 6 Hz or slower) to prevent
oL2 [Drive Overloaded]
.
1
(0, 1)
Note:
Contact Yaskawa or your nearest sales representative for consultation before disabling this function at low speeds. Frequent operation of
drives under conditions of high output current in low speed ranges may shorten the service life of the drive IGBT due to heat stress.
0 : Disabled (No Additional Derate)
The drive does not decrease the overload protection level.
1 : Enabled (Reduced oL2 Level)
When the drive detects
oL2
during low speed operation, it automatically decreases the overload detection level.
At zero speed, the drive derates the overload by 50%.
■
L8-18: Software Current Limit Selection
No.
(Hex.)
Name
Description
Default
(Range)
L8-18
(04BE)
Software Current Limit
Selection
Set the software current limit selection function to prevent damage to the main circuit transistor
caused by too much current.
0
(0, 1)
0 : Disabled
When the output current is at the software current limit value, the drive does not restrict the output voltage.
Note:
The drive may detect an
oC [Overcurrent]
when loads are particularly heavy or the acceleration time is particularly short.
1 : Enabled
When the output current is at the software current limit value, the drive decreases output voltage to decrease output
current.
When the output current decreases to the software current limit level, the drive starts usual operation.
■
L8-19: Freq Reduction @ oH Pre-Alarm
No.
(Hex.)
Name
Description
Default
(Range)
L8-19
(04BF)
Freq Reduction @ oH Pre-
Alarm
Sets the ratio at which the drive derates the frequency reference during an
oH
alarm.
20.0%
(10.0 - 100.0%)
When
L8-03 = 4 [Overheat Pre-Alarm Selection = Operate at Reduced Speed (L8-19)]
and an
oH
alarm is output,
this function is enabled.
■
L8-27: Overcurrent Detection Gain
No.
(Hex.)
Name
Description
Default
(Range)
L8-27
(04DD)
Overcurrent Detection Gain
Sets the PM motor overcurrent detection level as a percentage of the motor rated current value.
300.0%
(0.0 - 1000.0%)
Note:
•
The overcurrent detection function detects the lower of these two values:
–
Drive overcurrent level
–
Motor rated current ×
L8-27
/ 100
•
Set
L7-xx [Torque Limit]
parameters <
L8-27
.
•
When you set
L8-27 = 0.0
, it disables this function. In usual conditions, do not set
L8-27 = 0.0
. If the drive rated current is much higher
than the motor rated current, PM motor magnets can demagnetize if current flows at the drive overcurrent detection level.