300
YASKAWA
SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
Figure 5.60 Acceleration/Deceleration Time Gain through Analog Input
■
6: DC Injection Braking Current
Setting Value
Function
Description
6
DC Injection Braking
Current
Enters a signal to adjust the current level used for DC Injection Braking when the drive rated output current is 100%.
Note:
When you set this function, it will disable the setting value of
b2-02 [DC Injection Braking Current]
.
Figure 5.61 DC Injection Braking Current through Analog Input
■
7: Torque Detection Level
Setting Value
Function
Description
7
Torque Detection Level
Enters a signal to adjust the overtorque/undertorque detection level.
Note:
Use this function with
L6-01 [Torque Detection Selection 1]
. This parameter functions as an alternative to
L6-02 [Torque Detection Level 1]
.
■
8: Stall Prevent Level During Run
Setting Value
Function
Description
8
Stall Prevent Level During
Run
Enters a signal to adjust the stall prevention level during run if the drive rated current is 100%.
Note:
The Stall Prevent Level During Run is based on the smaller of these two values:
•
Analog input value of MFAI terminal
•
L3-06 [Stall Prevent Level during Run]
Summary of Contents for H6B1A002
Page 12: ...12 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 74: ...Page Intentionally Blank...
Page 76: ...Page Intentionally Blank...
Page 454: ...5 14 Z Bypass Parameters 454 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 590: ...8 6 Storage Guidelines 590 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 780: ...11 3 European Standards 780 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...