288
YASKAWA
SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
OFF : Safety circuit fault or RUN/READY
Terminal H1-HC or terminal H2-HC is OFF (Open) (safety circuit fault), or the two terminals are ON or have short
circuited (RUN/READY).
■
2F: Maintenance Notification
Setting Value
Function
Description
2F
Maintenance Notification
The terminal activates when drive components are at their estimated maintenance period.
Tells the user about the maintenance period for these items:
•
IGBT
•
Cooling fan
•
Capacitor
•
Soft charge bypass relay
Note:
Refer to
“
Alarm Outputs for Maintenance Monitors
”
for more information.
■
37: During Frequency Output
Setting Value
Function
Description
37
During Frequency Output
The terminal activates when the drive outputs frequency.
ON : The drive outputs frequency.
OFF : The drive does not output frequency.
Note:
The terminal deactivates in these conditions:
•
During Stop
•
During baseblock
•
During DC Injection Braking (initial excitation)
Figure 5.57 Active Frequency Output Time Chart
■
38: Drive Enabled
Setting Value
Function
Description
38
Drive Enabled
This terminal activates when the
H1-xx = 6A [Drive Enable]
terminal activates.
■
39: Watt Hour Pulse Output
Setting Value
Function
Description
39
Watt Hour Pulse Output
Outputs the pulse that shows the watt hours.
Note:
Refer to
“
H2-06: Watt Hour Output Unit Selection
”
for more information.
Summary of Contents for H6B1A002
Page 12: ...12 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 74: ...Page Intentionally Blank...
Page 76: ...Page Intentionally Blank...
Page 454: ...5 14 Z Bypass Parameters 454 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 590: ...8 6 Storage Guidelines 590 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 780: ...11 3 European Standards 780 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...