YASKAWA
SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
239
Figure 5.35 Jump Frequency
Note:
•
When you set Jump Frequencies 1 to 3, make sure that the parameters do not overlap.
•
When the drive is in the range of the Jump frequency, the frequency reference changes automatically. When Jump is executed, the output
frequency changes smoothly as specified by the values set in
C1-01 [Acceleration Time 1]
and
C1-02 [Deceleration Time 1]
.
■
d3-01: Jump Frequency 1
No.
(Hex.)
Name
Description
Default
(Range)
d3-01
(0294)
Jump Frequency 1
Sets the median value of the frequency band that the drive will avoid.
0.0 Hz
(0.0 - 400.0 Hz)
Note:
Set this parameter to 0.0 Hz to disable the Jump frequency.
■
d3-02: Jump Frequency 2
No.
(Hex.)
Name
Description
Default
(Range)
d3-02
(0295)
Jump Frequency 2
Sets the median value of the frequency band that the drive will avoid.
0.0 Hz
(0.0 - 400.0 Hz)
Note:
Set this parameter to 0.0 Hz to disable the Jump frequency.
■
d3-03: Jump Frequency 3
No.
(Hex.)
Name
Description
Default
(Range)
d3-03
(0296)
Jump Frequency 3
Sets the median value of the frequency band that the drive will avoid.
0.0 Hz
(0.0 - 400.0 Hz)
Note:
Set this parameter to 0.0 Hz to disable the Jump frequency.
■
d3-04: Jump Frequency Width
No.
(Hex.)
Name
Description
Default
(Range)
d3-04
(0297)
Jump Frequency Width
Sets the width of the frequency band that the drive will avoid.
1.0 Hz
(0.0 - 20.0 Hz)
Summary of Contents for H6B1A002
Page 12: ...12 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 74: ...Page Intentionally Blank...
Page 76: ...Page Intentionally Blank...
Page 454: ...5 14 Z Bypass Parameters 454 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 590: ...8 6 Storage Guidelines 590 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 780: ...11 3 European Standards 780 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...