A1-1
The Drive control circuits use various parameters to select functions and characteristics of the Drive.
Changing of parameter settings must be done in the Program mode, or by use of the Function
LEDs, if available (see Section 4).
The following table lists all parameters in numerical order. For each parameter, reference
paragraph(s) in Section 5 are listed (if applicable) where the features of the Drive affected by that
parameter are described.
Table A1-1. GPD 315/V7 Parameters
Appendix 1. LISTING OF PARAMETERS
PARA-
SETTING RANGE
SETTING
FACTORY
USER
PARA.
METER
NAME
(AND UNITS)
INCREMENT
SETTING
SETTING
REF.
0:
n001 can be read and set;
n002 - n179 read only
1:
n001 - n039 can be read and set
2:
n001 - n079 can be read and set
3:
n001 - n119 can be read and set
n001
Parameter Selection /
4:
n001 - n179 can be read and set
Initialization
5:
n001 - n179 can be read and set
1
1
5.21
6:
Clear Fault History Only
7:
Not Used
8:
2-wire Initialization (Japan Spec.)
9:
3-wire Initialization (Japan Spec.)
10: 2 wire initialization (USA Spec)
11: 3 wire initialization (USA Spec.)
n002
Control Method Selection
0:
V/f Control
1
0
2.2
1:
Open Loop Vector
0:
Digital Operator
n003
Operation Method Selection
1:
Terminal
1
1
5.13
2:
Serial Communication (Modbus)
3:
Option Card
0:
Digital Operator Pot
1:
Digital Operator
2:
Voltage Reference (0 to 10V)
3:
Current Reference (4 to 20 mA)
n004
Reference Selection
4:
Current Reference (0 to 20 mA)
5.11,
5:
Pulse Train Reference
1
2
5.13
6:
Serial Communications (Modbus)
7:
Multi-Function Analog Input (0 to 10V)
8:
Multi-Function Analog Input (4 to 20 mA)
9:
Option Card
n005
Stop Method
0:
Ramp to stop
1
0
5.24
1:
Coast to stop
n006
Reverse Prohibit
0:
Reverse Run enabled
1
0
1:
Reverse Run disabled
0:
STOP key is effective regardless of
programming of n003
n007
STOP Key Function
1:
STOP key is effective only when sequence
1
0
5.13
command (per n003) is from Digital Operator
0:
Frequency Reference from digital
n008
Reference Selection -
operator pot
1
0
5.13
Digital Operator
1:
Frequency Reference from n024
0:
ENTER key must be pressed to write-in
n009
Frequency Reference Setting
new value
1
0
5.13
Method From Digital Operator 1:
ENTER key does not have to be pressed
to write-in new value
Operation Selection
0:
Disabled (operation continues)
n010
When Digital Operator is
1:
Enabled (motor coasts to a stop and fault
1
0
5.15
Disconnected
is displayed)
n011
Frequency - Max.
50.0 to 400.0
0.1 (Hz)
60.0
n012
Voltage - Max.
0.1 to 255.0 (230V drive)
0.1 (V)
230.0
0.2 to 510.0 (460V drive)
460.0
n013
Frequency - Max.
0.2 to 400.0
0.1 (Hz)
60.0
Voltage Point
n014
Frequency - Midpoint
0.1 to 399.9
0.1 (Hz)
Note 2
5.27
n015
Voltage - Midpoint
0.1 to 255.0 (230V drive)
0.1 (V)
Note 2
0.2 to 510.0 (460V drive)
n016
Frequency - Min.
0.1 to 10.0
0.1 (Hz)
Note 2
n017
Voltage - Min.
0.1 to 50.0 (230V drive)
0.1 (V)
Note 2
0.2 to 100.0 (460V drive)
Summary of Contents for GPD315/V7-4X
Page 1: ...GPD 315 V7 and V7 4X Technical Manual...
Page 4: ......
Page 20: ...xvi...
Page 22: ......
Page 40: ...1 18...
Page 52: ...3 2...
Page 56: ...4 4...
Page 101: ...5 45 PID Block Diagram...
Page 130: ...A1 8...
Page 134: ...A3 2...
Page 136: ...A4 2...
Page 146: ...A6 6...
Page 150: ...A7 4...
Page 154: ...A8 4...
Page 158: ......
Page 160: ......