5-52
n 0 3 5 : Operator Display Mode
Factory setting: 0
Reference and Indication
Range: 0 to 3999
This parameter determines the scaling of the Digital Operator display, for both Output
Frequency and all Frequency References.
DATA
DISPLAY
0
Output frequency, in increments of 0.1 Hz.
(factory
setting)
1
Output frequency, in increments of 0.1 %.
2 t o 39
Motor synchronous speed (P =
(no. of motor
in increments of 1 RPM
poles)
(3999 max).
P = no. of motor poles
F = Frequency
N
S
= motor synchronous speed
NOTE: If motor synchronous speed exceeds
3999 RPM, display holds at 3 9 9 9 .
4 0
Line speed or other parameter.
t o
39 9 9
X X X X
Parameter value at maxi-
mum frequency (n 0 1 1 )
(include leading zeroes
if necessary)
Location of decimal point:
_ = _ X X X
1 = _ X X. X
2 = _ X. X X
3 = 0. X X X
EXAMPLE:
To display Line Speed, based on
54.3 FPM at 60 Hz:
n035 setting = " 15 4 3 "
DATA
DISPLAY
120 x F
)
N
S
5 . 3 0 D I G I T A L OPERATOR DISPLAY SELECTION