1 : Accept RUN while Programming
The drive accepts a Run command entered from an external source while in Programming Mode.
2 : Allow Programming Only at Stop
The drive does not let the user enter Programming Mode when the drive is operating. The drive does not show the
Programming Mode when a Run command is active.
■
b1-09: LOCAL/REMOTE Select during RUN
No.
(Hex.)
Name
Description
Default
(Range)
b1-09
(0188)
Expert
LOCAL/REMOTE Select
during RUN
Sets the function that lets you use the
during operation to switch between LOCAL and
REMOTE Modes.
0
(0, 1)
0 : Disabled
1 : Enabled
When you switch the operation mode from REMOTE to LOCAL during run, the drive writes this REMOTE operation
status to the keypad:
•
Frequency reference during run
•
RUN/STOP status of the keypad
•
FWD/REV
•
JOG
Note:
When b1-09 = 1, the drive will detect
oPE05 [Run Cmd/Freq Ref Source Sel Err]
if you set one of these parameter values:
•
b1-02 = 0 [Run Command Selection 1 = Keypad]
•
b1-16 = 0 [Run Command Selection 2 = Keypad] and H1-xx = 2 [MFDI Function Selection = External Reference 1/2 Selection]
•
H1-xx = 3 to 6, 12, 13, 32 [Multi-Step Speed Reference 1 to 4, Jog Reference Selection, Forward Jog, Reverse Jog]
■
b1-14: Phase Order Selection
No.
(Hex.)
Name
Description
Default
(Range)
b1-14
(01C3)
Phase Order Selection
Sets the phase order for output terminals U/T1, V/T2, and W/T3. This parameter can align the
Forward Run command from the drive and the forward direction of the motor without changing
wiring.
0
(0, 1)
0 : Standard
1 : Switch Phase Order
■
b1-15: Frequency Reference Selection 2
No.
(Hex.)
Name
Description
Default
(Range)
b1-15
(01C4)
Frequency Reference
Selection 2
Sets the input method for frequency reference 2.
0
(0 - 4)
This parameter is enabled when
H1-xx = 2 [MFDI Function Selection = External Reference 1/2 Selection]
is
activated.
Note:
•
Push
on the keypad to set the input mode to LOCAL and enter the frequency reference from the keypad.
•
If the frequency reference is 0 Hz or ≤
E1-09 [Minimum Output Frequency]
and the drive receives a Run command, the
on the keypad
will flash. Check the setting for the frequency reference input and enter a value more than or equal to
E1-09
.
0 : Keypad
Use the keypad to enter the frequency reference.
Use
and
on the keypad to change the frequency reference.
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
Summary of Contents for GA800 Series
Page 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Page 20: ...i 3 Warranty Information 20 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Page 58: ...2 9 Installation Methods 58 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Page 268: ...5 6 Safe Disable Input 268 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Page 306: ...6 3 MEMOBUS Modbus Communications 306 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Page 426: ...8 7 Storage Guidelines 426 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...