12.2 A: Initialization Parameters
YASKAWA
SIEPC71061737B GA800 Drive Technical Reference
643
•
A1-07 [DriveWorksEZ Function Selection]
•
A2-01 to A2-32 [User Parameter 1 to 32]
To lock parameter settings after making changes without changing the password, enter the incorrect password in
A1-
04
and push
.
Enter the Password to Unlock Parameters
Use this procedure to unlock parameter settings.
Set the password in
A1-05 [Password Setting]
, and show the Parameter Setting Mode screen on the keypad.
This procedure verifies the password, and makes sure that the parameter settings are unlocked.
1.
Push
or
to select “A: Initialization Parameters”, then push
.
2.
Push
or
to select
[A1-04]
, then push
.
You can now change parameter settings.
3.
Push
or
to move the digit and enter the password.
4.
Push
to confirm the password.
The drive unlocks the parameters and automatically shows the Parameters Screen.
5.
Push
or
to show
[A1-02]
, then push
.
The keypad shows the setting value for
[A1-02]
.
6.
Push
or
to make sure that you can change the setting value.
Push
(Back) until the keypad shows the Parameter Setup Mode screen.
■
A1-05: Password Setting
No.
(Hex.)
Name
Description
Default
(Range)
A1-05
(0105)
Password Setting
Set the password to lock parameters and prevent changes to parameter settings. Enter the correct
password in
A1-04 [Password]
to unlock parameters and accept changes.
0000
(0000 - 9999)
This parameter can lock these parameter settings:
•
A1-01 [Access Level Selection]
•
A1-02 [Control Method Selection]
•
A1-03 [Initialize Parameters]
•
A1-06 [Application Preset]
•
A1-07 [DriveWorksEZ Function Selection]
•
A2-01 to A2-32 [User Parameter 1 to 32]
Note:
•
Usually, the keypad will not show
A1-05
. To show and set
A1-05
, show
A1-04 [Password]
and then push
and
on the keypad at
the same time.
•
After you set
A1-05
, the keypad will not show it again until you enter the correct password in
A1-04
. Make sure that you remember the
A1-
05
setting value. If you do not know the
A1-05
setting value, contact Yaskawa or your nearest sales representative.
•
When
A1-03 = 2220, 3330 [2-Wire Initialization, 3-Wire Initialization]
, the drive is initialized to
A1-05 = 0000
. Be sure to set the password
again when a password is necessary for the application.
•
Change the setting value in
A1-05
to change the password. The new setting value becomes the new password.
•
When you use the password to unlock and change a parameter, enter a value other than the password in
A1-04
to lock the parameter again
with the same password.
•
If
A1-04
≠
A1-05
, MEMOBUS Communication cannot read or write
A1-05
.
■
A1-06: Application Preset
WARNING!
Sudden Movement Hazard. Check the I/O signals and the external sequences for the drive before you set the
Application Preset function. When you set the Application Preset function (A1-06
≠
0), it changes the I/O terminal functions for the
drive and it can cause equipment to operate unusually. This can cause serious injury or death.
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
Summary of Contents for GA800 Series
Page 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Page 20: ...i 3 Warranty Information 20 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Page 58: ...2 9 Installation Methods 58 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Page 268: ...5 6 Safe Disable Input 268 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Page 306: ...6 3 MEMOBUS Modbus Communications 306 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Page 426: ...8 7 Storage Guidelines 426 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...