7.10 Troubleshooting Without Fault Display
YASKAWA
SIEPC71061737B GA800 Drive Technical Reference
369
◆
The Motor Is Making an Audible Noise
Causes
Possible Solutions
100% of the rated output current of the drive was exceeded while operating at
low speeds.
•
If the sound is coming from the motor, set
L8-38 = 0 [Carrier Frequency Reduction = Disabled]
.
•
If
oL2 [Drive Overloaded]
occurs frequently after setting
L8-38 = 0
, replace the drive with a
high-capacity drive.
◆
The Motor Will Not Restart after a Loss of Power
Causes
Possible Solutions
The drive did not receive a Run command after applying power.
•
Examine the sequence and wiring that enters the Run command.
•
Set up a relay to make sure that the Run command stays enabled during a loss of power.
For applications that use 3-wire sequence, the momentary power loss continued
for a long time, and the relay that keeps the Run command has been switched
off.
Examine the wiring and circuitry for the relay that keeps the Run command enabled during the
momentary power loss ride-thru time.
Summary of Contents for GA800 Series
Page 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Page 20: ...i 3 Warranty Information 20 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Page 58: ...2 9 Installation Methods 58 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Page 268: ...5 6 Safe Disable Input 268 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Page 306: ...6 3 MEMOBUS Modbus Communications 306 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Page 426: ...8 7 Storage Guidelines 426 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...