YASKAWA
TOEPYAIGA8002B GA800 Drive Programming
429
■
H6-05: Terminal RP Filter Time
No.
(Hex.)
Name
Description
Default
(Range)
H6-05
(0430)
RUN
Terminal RP Filter Time
Sets the time constant for the pulse train input primary delay filters.
0.10 s
(0.00 - 2.00 s)
■
H6-06: Terminal MP Monitor Selection
No.
(Hex.)
Name
Description
Default
(Range)
H6-06
(0431)
RUN
Terminal MP Monitor
Selection
Sets a function for pulse train monitor output terminal MP. Sets the
“
x-xx
”
part of the
Ux-xx
monitor.
102
(000, 031, 101, 102, 105,
116, 501, 502, 801 - 809,
821 - 825, 831 - 839, 851 -
855)
Note:
To use in through mode or when terminal MP is not used, set this parameter to 000 or 031.
When you use the pulse train monitor, make sure that you connect peripheral devices as specified by these load
conditions:
Incorrect connections can make the characteristics not sufficient or cause mechanical damage.
•
Use the pulse train monitor as the sourcing output.
Output Voltage
VRL(V)
Load Impedance (k
Ω
)
5 V or more
1.5 kΩ or more
8 V or more
4.0 kΩ or more
10 V or more
10 kΩ or more
Figure 2.115 Circuit Diagram When Used as the Sourcing Output
•
Use the pulse train monitor as the sinking input
External Power Supply (V)
12 VDC
±
10%, 15 VDC
±
10%
Sinking current (mA)
16 mA or less
Figure 2.116 Circuit Diagram When Used as the Sinking Input