408
YASKAWA
TOEPYAIGA8002B GA800 Drive Programming
Note:
•
Refer to H3-xx
“
MFAI Setting Values
”
for the analog input setting values.
•
When you will not use the terminal, set
H3-40 to H3-42 = F
. The through mode function is not supported.
•
You cannot use
H3-40 to H3-42
to set these MFAI terminals:
H3-xx Setting Value
Function
0
Frequency Reference
1
Frequency Gain
2
Auxiliary Frequency Reference 1
3
Auxiliary Frequency Reference 2
30
DWEZ Analog Input 1
31
DWEZ Analog Input 2
32
DWEZ Analog Input 3
◆
H3: MFAI Parameters
■
H3-01: Terminal A1 Signal Level Select
No.
(Hex.)
Name
Description
Default
(Range)
H3-01
(0410)
Terminal A1 Signal Level
Select
Sets the input signal level for MFAI terminal A1.
0
(0 - 3)
0 : 0 to 10V (Lower Limit at 0)
The voltage signal is 0 Vdc to 10 Vdc. The minimum input level limit is 0%. The drive will read a negative input
signal caused by gain and bias settings as 0%.
1 : -10 to +10V (Bipolar Reference)
The voltage signal is -10 Vdc to 10 Vdc. This setting enables positive and negative polarity signals. When the drive
uses this setting as the frequency reference, a Forward Run command will run the motor in reverse and a Reverse Run
command will run the motor forward. The gain and bias settings will cause the signal to be a negative number.
2 : 4 to 20 mA
The current signal is 4 mA to 20 mA. The minimum input level limit is 0%. The drive will read a negative input
signal caused by gain and bias settings as 0%.
3 : 0 to 20 mA
The current signal is 0 mA to 20 mA. The minimum input level limit is 0%. The drive will read a negative input
signal caused by gain and bias settings as 0%.
Note:
When
H3-01 = 0, 1
, set DIP switch S1-1 to the V side (voltage). When
H3-01 = 2, 3
, set DIP switch S1-1 to the I side (current). The default
setting is the V side (voltage).
■
H3-02: Terminal A1 Function Selection
No.
(Hex.)
Name
Description
Default
(Range)
H3-02
(0434)
Terminal A1 Function
Selection
Sets the function for MFAI terminal A1.
0
(0 - 32)
■
H3-03: Terminal A1 Gain Setting
No.
(Hex.)
Name
Description
Default
(Range)
H3-03
(0411)
RUN
Terminal A1 Gain Setting
Sets the gain of the analog signal input to MFAI terminal A1.
100.0%
(-999.9 - +999.9%)
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV