D : Const Trq, 60 Hz base, 120 Hz max
Use this constant output pattern to rotate motors at more than 60 Hz. Output voltage is constant when you operate at
more than 60 Hz.
Note:
The voltage values in the figures are for 200 V class drives. Multiply the values by 2 for 400 V class drives.
HD: 2004 - 2021, 4002 - 4012
ND: 2004 - 2018, 4002 - 4009
HD: 2030 - 2211, 4018 - 4103
ND: 2021 - 2169, 4012 - 4089
HD: 2257 - 2415, 4140 - 4720
ND: 2211 - 2415, 4103 - 4720
E : Const Trq, 60 Hz base, 180 Hz max
Use this constant output pattern to rotate motors at more than 60 Hz. Output voltage is constant when you operate at
more than 60 Hz.
Note:
The voltage values in the figures are for 200 V class drives. Multiply the values by 2 for 400 V class drives.
HD: 2004 - 2021, 4002 - 4012
ND: 2004 - 2018, 4002 - 4009
HD: 2030 - 2211, 4018 - 4103
ND: 2021 - 2169, 4012 - 4089
HD: 2257 - 2415, 4140 - 4720
ND: 2211 - 2415, 4103 - 4720
F : Custom
Set
E1-04
to
E1-13 [V/f Pattern for Motor 1]
to set the values for this custom pattern.
The default settings are the same as setting value
1 [Const Trq, 60Hz base, 60Hz max]
.
■
E1-04: Maximum Output Frequency
No.
(Hex.)
Name
Description
Default
(Range)
E1-04
(0303)
Maximum Output Frequency
Sets the maximum output frequency for the V/f pattern.
Determined by A1-02 and
E5-01
(Determined by A1-02 and
E5-01)
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV