YASKAWA
TOEPYAIGA8001B GA800 Drive Maintenance & Troubleshooting
95
Code
Name
Causes
Possible Solutions
The drive output circuit is broken.
•
Re-energize the drive.
•
If the fault stays, replace the control board or the drive. For
information about replacing the control board, contact Yaskawa
or your nearest sales representative.
Note:
•
The drive detects this fault if there is not balance between the three phases of the output current from the PM motor.
•
Do a Fault Reset to clear the fault.
Code
Name
Causes
Possible Solutions
LSo
Low Speed Motor Step-Out
The motor code set incorrectly.
•
Set
E5-01 [PM Motor Code Selection]
correctly as specified by
the motor.
•
For specialized motors, refer to the motor test report and set
E5-
xx
correctly.
The load is too large.
•
Decrease the load.
•
Replace the drive and motor with larger capacity models.
An external force on the load side caused the motor to
move at start.
Find and repair problems on the load side that cause the motor to
rotate from the load side.
The drive incorrectly detected the motor magnetic
pole position.
•
Set
b3-01 = 1 [Speed Search at Start Selection = Enabled]
.
•
If the value for
U6-57 [PolePolarityDeterVal]
is lower than 819,
increase the value set in
n8-84 [Polarity Detection Current]
.
Consult the motor manufacturer for information about maximum
setting values.
The setting of
n8-84 [Polarity Detection Current]
is
too low.
Increase the n8-84 setting from the default. Consult the motor
manufacturer for information about maximum setting values.
Incorrect values set in
L8-93 [Low Speed Pull-out
DetectionTime]
,
L8-94 [Low Speed Pull-out Detect
Level]
, and
L8-95 [Low Speed Pull-out Amount]
.
Increase the values set in
L8-93 to L8-95.
The drive incorrectly detected the motor magnetic
pole position.
If you are using an IPM motor, do High Frequency Injection Auto-
Tuning.
Note:
•
The drive detects this fault if it detects step-out while running at low speed.
•
Do a Fault Reset to clear the fault.
•
LSo
is a protective function that stops the motor and stops the reverse run if a motor without a motor code incorrectly detects the initial polarity. To quickly detect motor reversal,
decrease the values set in
L8-93
to
L8-95
to a range in which the drive does not malfunction.
Code
Name
Causes
Possible Solutions
nSE
Node Setup Error
The
H1-xx = 47 [Node Setup (CANopen)]
terminal
was activated during run.
The drive received a Run command while the Node
Setup function was active.
Stop the drive when the Node Setup function is in use.
Note:
Do a Fault Reset to clear the fault.
Code
Name
Causes
Possible Solutions
oC
Overcurrent
The load is too heavy.
•
Measure the current flowing into the motor.
•
Replace the drive with a larger capacity model if the current
value is more than the drive rated current.
•
Decrease the load or replace with a larger drive to prevent
sudden changes in the current level.
Overheating caused damage to the motor or the motor
insulation is not satisfactory.
Measure the motor insulation resistance, and replace the motor if
there is electrical conduction or unserviceable insulation.
The motor main circuit cable is contacting ground to
make a short circuit.
•
Examine the motor main circuit cable for damage, and repair
short circuits.
•
Measure the resistance between the motor main circuit cable and
the ground terminal. If there is electrical conduction, replace the
cable.
A short circuit or ground fault on the drive output
side caused damage to the output transistor of the
drive.
•
Make sure that there is not a short circuit in terminal B1 and
terminals U/T1, V/T2, and W/T3. Make sure that there is not a
short circuit in terminals - and terminals U/T1, V/T2, and W/T3.
•
If there is a short circuit, contact Yaskawa or your nearest sales
representative.
The acceleration time is too short.
•
Calculate the torque necessary during acceleration related to the
load inertia and the specified acceleration time.
•
Increase the values set in
C1-01, C1-03, C1-05, or C1-07
[Acceleration Times]
to get the necessary torque.
•
Increase the values set in
C2-01 to C2-04 [S-Curve
Characteristics]
to get the necessary torque.
•
Replace the drive with a larger capacity model.
Summary of Contents for GA800 Series
Page 2: ...This Page Intentionally Blank 2 YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance Troubleshooting...
Page 18: ...i 2 Using the Product Safely 18 YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance Troubleshooting...
Page 72: ...1 7 Storage Guidelines 72 YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance Troubleshooting...
Page 336: ...4 10 Installation Methods 336 YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance Troubleshooting...
Page 565: ...YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance Troubleshooting 565...